Powerware
Plus 18

Technical Specifications
12-18
kVA
- Model
12 - 12kVA/8kW
- Model
15 - 15 kVA/10kW
- Model
18 - 18kVA/12kW
|
|
|
Input
|
|
Voltage
Range
|
See
table below
|
|
Frequency
Range
|
45-65
Hz
|
|
Surge
Protection
|
Meets
IEEE 587/ANSI C62.41, Category A & B
|
| Power
Factor |
0.95
Typical at full load |
|
Output
|
|
Voltage
Regulation
|
Better
than +/- 3%
|
|
Voltage
THD
|
Less
than 5% (100% nonlinear load); Less than 3%
(100% linear load)
|
|
Transient
Response
|
Less
than 5% for 100% load, step full recovery within
1/4 cycle
|
| Frequency
Regulation |
(Free
Run) +/- 0.1 Hz |
| Frequency
Sync Range |
+/-
1.0 Hz |
| Frequency
Slew Rate |
1
Hz/sec. |
| Load
Crest Ratio |
3:1 |
| Common
Mode Noise Rejection |
>100
dB |
|
Battery
|
|
Battery
Type
|
Sealed,
maintenance-free lead acid
|
| Battery
Voltage |
240
VDC
|
|
Recharge
time
|
12x
discharge to 90% capacity
|
| Safety |
UL
1778 Listed
CUL CAN/CSA C22.2NO.107.1-M91 Listed
EN 50091-1
All Cabinets provide seismic mounting features |
|
Environmental
and safety
|
|
Audible
Noise
|
<60
dBA at 1 meter
|
|
Ambient
Operating Temperature
|
0C
to 40C
|
|
Ambient
Storage Temperature
|
-20C
to +70C
|
| Altitude |
5000
ft. (1500 m) without derating |
|
Relative
Humidity
|
5-95%
minimum non-condensing
|
| EMI
Suppression |
Meet
FCC Class A, Subpart J of Part 15 |
| Electrostatic
Discharge |
Withstands
25kV without damage or disturbance to load |
*
subject to change without notice.
Model Selection Guide
|
Nominal
Voltage*
(Line-Line)
|
Input
Voltage
|
Model
12kVA/8kW
|
Model
15kVA/10kW
|
Model
18kVA/12kW
|
|
Max.
|
Maximum
Rated
Current Per Phase
|
Max.
|
Maximum
Rated
Current Per Phase
|
Max.
|
Maximum
Rated
Current Per Phase
|
|
Input
|
Output
|
Range
|
kVA
|
Input
|
Output
|
kVA |
Input
|
Output
|
kVA |
Input |
Output |
|
200
|
200
|
176-253
|
11.7
|
29A
|
34A
|
14.5 |
36A |
42A |
17.2 |
43A |
50A |
|
208
|
208
|
176-253
|
12.2
|
28A
|
34A
|
15 |
35A |
42A |
18 |
42A |
50A |
|
220
|
220
|
176-253
|
11.8
|
26A
|
31A
|
14.8 |
33A |
39A |
17.9 |
39A |
47A |
|
|
Model
12kVA/8kW HV
|
Model
15kVA/10kW HV
|
Model
15kVA/10kW HV
|
|
380
|
380
|
367-391
|
12
|
15A
|
18A
|
15 |
19A |
23A |
18
|
23A |
27A |
|
400
|
400
|
388-412
|
11.9
|
14A
|
17A
|
15 |
18A |
22A |
17.9
|
22A |
26A |
|
415
|
415
|
403-427
|
12
|
14A
|
17A
|
15.6 |
18A |
22A |
18
|
21A |
25A |
|
480
|
480
|
467-494
|
11.6
|
12A
|
14A
|
15 |
15A |
18A |
18.3
|
18A |
22A |
|
480
|
208
|
467-494
|
11.9
|
12A
|
33A
|
15.1 |
15A |
42A |
18
|
18A |
50A |
| *
Nominal UPS module input/voltage, i.e If unit
is being used as a voltage or frequency converter,
the bypass must be disabled. Input/Output voltage,
phase and frequency must be equal for bypass operation.
Line to neutral voltage=line to line divided by
1.73 |
|
Battery Run Times (in minutes)
|
Output Watts |
Standard
Battery Configuration |
2
EBC2 Cabs |
1
EBC1 Cab** + 2 EBC2 Cabs*** |
3
EBC2 Cabs*** |
| 1000 |
146 |
198 |
250 |
301 |
| 2000 |
76 |
105 |
133 |
161 |
| 3000 |
50 |
70 |
89 |
109 |
| 4000 |
37 |
52 |
68 |
83 |
| 5000 |
28 |
40 |
52 |
65 |
| 6000 |
22 |
33 |
43 |
53 |
| 7000 |
18 |
27 |
36 |
44 |
| 8000 |
15 |
22 |
30 |
38 |
| 9000 |
12 |
19 |
26 |
33 |
| 10,000 |
10 |
16 |
22 |
29 |
| 11,000 |
8 |
14 |
20 |
25 |
| 12,000 |
7 |
12 |
17 |
22 |
*Estimated
accuracy of battery support times is +/-10%.
**EBC1 is one half-full battery cabinet.
***EBC2 is one full battery cabinet.
|
| |
|