Powerware
Plus 36
Technical
Specifications
24
- 36 kVA
- Model
24 - 24kVA/16kW
200/115 - 220/127 VAC
- Model
36 - 36 kVA/24kW
200/115 - 220/127 VAC
|
|
|
Input
|
|
Voltage
Range
|
See
table below
|
|
Frequency
Range
|
45-65
Hz
|
|
Surge
Protection
|
Meets
ANSI C62.41, Category A & B
|
| Power
Factor |
0.95
Typical at full load |
|
Output
|
|
Voltage
Regulation
|
Better
than +/- 2%
|
|
Voltage
THD
|
Less
than 5% (100% nonlinear load); Less than 3%
(100% linear load)
|
|
Transient
Response
|
Less
than 5% for 100% load, step full recovery within
1/4 cycle
|
| Frequency
Regulation |
(Free
Run) +/- 0.1 Hz |
| Frequency
Sync Range |
+/-
1.0 Hz |
| Frequency
Slew Rate |
1
Hz/sec. |
| Load
Crest Ratio |
3:1 |
| Common
Mode Noise Rejection |
>85
dB |
|
Battery
|
|
Battery
Type
|
Sealed,
maintenance-free lead acid
|
| Battery
Voltage |
240
VDC
|
|
Recharge
time
|
12x
discharge to 90% capacity
|
| Safety |
UL
1778 Listed
CUL CAN/CSA C22.2NO.107.1-M91 Listed
All Cabinets provide seismic mounting features |
|
Environmental
and safety
|
|
Audible
Noise
|
<60
dBA at 1 meter
|
|
Ambient
Operating Temperature
|
0C
to 40C
|
|
Ambient
Storage Temperature
|
-20C
to +60C
|
| Altitude |
5000
ft. (1500 m) without derating |
|
Relative
Humidity
|
5-95%
minimum non-condensing
|
| EMI
Suppression |
Meet
FCC Class A, Subpart J of Part 15 |
| Electrostatic
Discharge |
Withstands
25kV without damage or disturbance to load |
*
Specifications subject to change without notice.
Model
Selection Guide
- Model
24 - 24kVA/16kW
200/115 - 220/127 VAC
- Model
36 - 36 kVA/24kW
200/115 - 220/127 VAC
|
Nominal
Voltage*
(Line-Line)
|
Input
Voltage
|
Model
24
|
Model
36
|
|
Max.
|
Nominal
|
Maximum
Rated
Current Per Phase
|
Max.
|
Nominal |
Maximum
Rated
Current Per Phase
|
|
Input
|
Output
|
Range
|
kVA
|
KW
|
Input
|
Output
|
kVA |
KW
|
Input
|
Output
|
|
200
|
200
|
176-253
|
23.1
|
16
|
58A
|
67A
|
34.5
|
24
|
87A |
100A |
|
208
|
208
|
176-253
|
24.1
|
16
|
56A
|
67A
|
36
|
24
|
84A |
100A |
|
220
|
220
|
176-253
|
23.6
|
16
|
53A
|
67A
|
35.8
|
24
|
79A |
94A |
|
|
Model
24 HV
|
Model
36 HV
|
|
380
|
380
|
323-552
|
23.8
|
16
|
35A
|
36A
|
35.6 |
24
|
53A |
54A |
|
380
|
208
|
323-552 |
24.1 |
16
|
35A |
67A
|
36 |
24
|
53A |
100A |
|
400
|
400
|
340-485
|
24.2
|
16
|
34A
|
35A
|
35.9 |
24
|
51A |
52A |
|
400
|
208
|
340-485 |
24.1 |
16
|
34A |
67A
|
36 |
24
|
51A |
100A |
|
415
|
415
|
353-500
|
23.8
|
16
|
32A
|
33A
|
36 |
24
|
49A |
50A |
|
415
|
208
|
353-500 |
24.1 |
16
|
32A |
67A
|
36 |
24
|
49A |
100A |
|
480
|
480
|
410-580
|
24.1
|
16
|
28A
|
29A
|
35.7 |
24
|
42A |
43A |
|
480
|
208
|
410-580
|
24.1
|
16
|
28A
|
67A
|
36 |
24
|
42A |
100A |
|
Nominal
Voltage*
(Line-Line)
|
Input
Voltage
|
Model
24
|
Model
36
|
|
Max.
|
Nominal
|
Maximum
Rated
Current Per Phase
|
Max.
|
Nominal |
Maximum
Rated
Current Per Phase
|
|
Input
|
Output
|
Range
|
kVA
|
KW
|
Input
|
Output
|
kVA |
KW
|
Input
|
Output
|
|
200
|
200
|
176-253
|
23.1
|
16
|
58A
|
67A
|
34.5
|
24
|
87A |
100A |
|
208
|
208
|
176-253
|
24.1
|
16
|
56A
|
67A
|
36
|
24
|
84A |
100A |
|
220
|
220
|
176-253
|
23.6
|
16
|
53A
|
67A
|
35.8
|
24
|
79A |
94A |
|
|
Model
24 HV
|
Model
36 HV
|
|
380
|
380
|
323-552
|
23.8
|
16
|
35A
|
36A
|
35.6 |
24
|
53A |
54A |
|
380
|
208
|
323-552 |
24.1 |
16
|
35A |
67A
|
36 |
24
|
53A |
100A |
|
400
|
400
|
340-485
|
24.2
|
16
|
34A
|
35A
|
35.9 |
24
|
51A |
52A |
|
400
|
208
|
340-485 |
24.1 |
16
|
34A |
67A
|
36 |
24
|
51A |
100A |
|
415
|
415
|
353-500
|
23.8
|
16
|
32A
|
33A
|
36 |
24
|
49A |
50A |
|
415
|
208
|
353-500 |
24.1 |
16
|
32A |
67A
|
36 |
24
|
49A |
100A |
|
480
|
480
|
410-580
|
24.1
|
16
|
28A
|
29A
|
35.7 |
24
|
42A |
43A |
|
480
|
208
|
410-580
|
24.1
|
16
|
28A
|
67A
|
36 |
24
|
42A |
100A |
| *
Nominal UPS module input/voltage, i.e If unit
is being used as a voltage or frequency converter,
the bypass must be disabled. Input/Output voltage,
phase and frequency must be equal for bypass operation.
Line to neutral voltage=line to line divided by
1.73 |
|
Battery Run Times
(in minutes)
|
Output
Watts
|
1
Battery Cabinet
|
2
Battery Cabinets
|
3
Battery Cabinets
|
| 8000 |
30 |
80 |
128 |
| 9000 |
25 |
72 |
110 |
| 10,000 |
22 |
65 |
98 |
| 11,000 |
20 |
57 |
88 |
| 12,000 |
18 |
50 |
78 |
| 13,000 |
15 |
45 |
70 |
| 14,000 |
14 |
40 |
62 |
| 15,000 |
13 |
35 |
56 |
| 16,000 |
12 |
30 |
50 |
| 17,000 |
11 |
27 |
47 |
| 18,000 |
10 |
24 |
43 |
| 19,000 |
9 |
22 |
40 |
| 20,000 |
8 |
20 |
37 |
| 21,000 |
7 |
18 |
35 |
| 22,000 |
6 |
17 |
33 |
| 23,000 |
5 |
16 |
31 |
| 24,000 |
5 |
15 |
30 |
Brochures
|
|
|
|