Feature |
Power Xpert 4000 |
Power Xpert 6000 |
Power Xpert 8000 |
| Embedded Web Server |
• |
• |
• |
| Power Quality Index (at-a-glance 'thermometer' view of power quality) |
• |
• |
• |
| TOU metering support |
• |
• |
• |
| Firmware flash upgrade support |
• |
• |
• |
| Self-learning capability (characterizes "normal" per circuit) |
• |
• |
• |
| Voltage, current: per phase minimum, maximum, average, trend graph analysis, export, print |
• |
• |
• |
| Power: power factor, apparent, real, reactive, frequency |
• |
• |
• |
| Energy, demand: forward, reverse, net, sum, TOU, profile, previous month comparison, graph analysis, export, print |
• |
• |
• |
| Statistical analysis (min, max, average) |
• |
• |
• |
| Sag and swell monitoring |
• |
• |
• |
| Symmetrical components: zero, negative, positive |
• |
• |
• |
| Low frequency transient detection and capture |
• |
• |
• |
| Sampling rate, maximum samples/cycle |
1024* |
1024* |
100,000 |
| "Number of nines" uptime data (e.g. 6 nines=99.9999%) |
• |
• |
• |
| Secure 5 level user access privileges |
• |
• |
• |
| Modbus TCP |
• |
• |
• |
| Modbus RTU |
• |
• |
• |
| HTML |
• |
• |
• |
| SNMP (Simple Network Management Protocol) |
• |
• |
• |
| SMTP (Simple Mail Transfer Protocol) |
• |
• |
• |
| FTP (File Transfer Protocol) |
• |
• |
• |
| NTP (Network Time Protocol) |
• |
• |
• |
| COMTRADE file format for waveform capture export |
• |
• |
• |
| Trend measurements CSV file export |
• |
• |
• |
| I/O (eight digital inputs, three relay outputs, two solid state KYZ outputs) |
• |
• |
• |
| NTP time synchronization up to 1 millisecond accuracy |
• |
• |
• |
| GPS time synchronization up to 1 millisecond accuracy |
• |
• |
• |
| Trend logging |
• |
• |
• |
| Load profile |
• |
• |
• |
| Event logging |
• |
• |
• |
| 512 MB standard, 1 GB optional memory |
• |
• |
• |
| Harmonics (phase angle and magnitude) |
127 |
127 |
127 |
| Delta-Sigma D/A Conversion Technology |
• |
• |
• |
| Harmonics over-sampling (1024 samples per cycle) |
• |
• |
• |
| Anti-alias filtering |
• |
• |
• |
| Flicker calculations |
|
• |
• |
| Sub-cycle disturbance capturing |
• |
• |
• |
| dV/dt triggers for sub-cycle oscillatory transients |
• |
• |
• |
| Absolute threshold and dV/dt triggering |
• |
• |
• |
| Automatic trigger setting |
|
• |
• |
| Automatic event severity analysis |
|
• |
• |
| ITIC (Information Technology Industry Council) performance curve |
|
• |
• |
| 6 MHz capture of impulsive transients |
|
|
• |
| Transient capture duration: ~20 ms/6MHz ~120 ms/1 MHz |
|
|
• |
| Waveform recorded at 100,000 samples per cycle |
|
|
• |
| Three-phase voltage and neutral-to-ground fast transient capture |
|
|
• |