The new Power Xpert® line of Electronic Meters has three main series and each provide unique additional functions.
-
The Power Xpert 4000 Meter
Provides core functions for monitoring power consumption and power quality. This unit uses Delta Sigma technology to sample circuits at 1024 samples per cycle for extremely accurate measurement of harmonics and other events.
-
The Power Xpert 6000 Meter
Adds another level of sampling ability, using a combination of voltage and duration to isolate sub-cycle oscillatory transients. An optional 512MB memory card provides generous storage for waveforms and other event data.
- The Power Xpert 8000 Meter
Adds the ability to capture very fast transients by sampling at 6 MHz — 100,000 samples per cycle. That’s a sample every 166 nanoseconds—six samples every millionth of a second, across three input channels and neutral-to-ground.
All Power Xpert Meters Features
- Embedded Web Server - see and analyze waveforms, trends, harmonics directly in your web browser or LCD meter graphic display
- Automatic power quality analysis and trigger setting with built-in ITIC performance curve: detect and capture sags, swells, transients, harmonics, flicker
- Accurately detect fast transients that previous generation monitors would miss, by assessing circuit activity at very high sampling rates (up to 100,000 samples per cycle)
- Comprehensive power, energy and demand measurements for 138 standard data points logged
- Voltage, current: per phase minimum, maximum, average, trend graph analysis, export, print
- Power: power factor, apparent, real, reactive, frequency
- Energy, demand: forward, reverse, net, sum, TOU, profile, previous month comparison, graph analysis, export, print
- Up to 1 millisecond time synchronization and event logging capability for sequence of events analysis
- At-a-glance view of power quality analysis with patent pending Power Quality Index gauge, statistically derived trending and red-yellow-green indicators for overall power health
- 24x7 support with continuous monitoring with a permanently installed meter
- Reduced cost of power quality monitoring
- Alarm notifications are also available remotely via e-mail
- Industry-standard communication protocols, to support a multitude of configurations and third-party software: HTTP, FTP, Modbus RTU, Modbus TCP, SNMP, SMTP, NTP, COMTRADE
- 1 GB data storage capability
- Supports Power Xpert software and hardware components
- ANSI C12.20 accuracy
The Power Xpert® Meters can be used in various applications including the following:
Energy Management
- Reduce Peak Demand Charges and Power Factor Penalties
- Identify Excessive Energy Consumption
Monitor Circuit Loading
- Avoid Overloads and Nuisance Overload Trips
- Maximize Equipment Utilization
- Manage Emergency Overloads
Identify Power Quality Problems
- Avoid Damage to Motors
- Reduce Interruptions to processes
- Avoid Blown Capacitor Bank Fuses
- Reduce the Overheating of Transformers and Conductors
Applications
Identify power quality problems
- Identify harmonics, sags, swells and transients damaging or
disrupting sensitive, mission critical IT equipment
- Boost IT equipment service life to the maximum
- Analyze sequence of events up to one millisecond time resolution
- Protect motors from damage
- Preserve the integrity of processes and batches
- Prevent blown capacitor bank fuses
- Protect transformers and conductors from overheating
Detect and record high speed transients
Detect and record high speed transients- Avoid equipment damage and disruption
- Identify equipment malfunction
Monitor circuit loading
Detect and record high speed transients
- Avoid overloads and nuisance overload trips
- Maximize equipment utilization
- Manage emergency overloads
Manage energy utilization
Manage energy utilization
- Reduce peak demand charges and power factor penalties
- Identify excessive energy consumption
1 millisecond time resolution - most accurate time available
Harmonics, voltage fluctuations, transient overvoltage conditions
and other power anomalies can wreak havoc on your equipment
and processes. It is essential to fully understand the quality of the
power that is being delivered throughout the facility. Detailed event
information makes it possible to pinpoint the root causes of problems—
or prevent them from occurring. With up to one millisecond
time stamping accuracy available via GPS and IRIG-time sources,
Power Xpert Meters register the sequence of events in a time-synchronized
environment. Based on National Institute of Standards
and Technology (NIST) atomic time, you can count on the most accurate
time available. In the past, basic power monitors were used to
identify existing conditions on an electrical distribution system or
to evaluate past problems. If you wanted to detect fast voltage transients,
you had to bring in portable power quality monitors that cost
up to $20,000 and usually required an outside consultant.
Built-in graphing - six samples every millionth of a second
Power Xpert 4000/6000/8000 next-generation meters redefine the
art of measuring and monitoring power quality. Thanks to the latest
technologies, these metering instruments are able to measure,
trend, analyze and capture waveforms while serving web pages to
users over the Internet, along with simultaneous FTP downloading
and comma separated values (CSV) exporting capabilities. No matter
if you are a PhD level power quality engineer or an IT system
administrator, these instruments will provide you with the level
of information you need, in an easy to understand graphical user
interface at astonishing speeds of six samples every millionth of a
second, if necessary.
Easy to use interface - demystifies power quality
In designing these power quality instruments,
Eaton set out to demystify power
quality—to take highly specialized data
and convert it into useful information that
doesn’t require a power guru or consultant
to understand. The result is an uncommonly
easy-to-use interface and new
graphical analysis of complex power quality
data—delivered via email, over the Web
and to third-party applications. With these
capabilities, your power team can predict
and prevent power quality problems before
they lead to equipment malfunction, overheated
circuits and system failure.
1 gigabyte of storage capability - store and trend 5-10 years worth of data
Having enough storage capacity is a critical
factor at this level of power quality instrumentation.
How long can I store data locally
on the power quality meter before the system will have to start
overwriting previously captured information? A Power Xpert Meter
has 512 MB of storage as standard and can be upgraded all the way
to 1 GB. In a typical power quality environment this would provide
storage capability for 5-10 years depending on the meter model.
Estimated memory and storage capacity
With 512 MB standard and 1 GB optional CompactFlash
| |
Occurrence per month* |
Memory Usage (MB) |
Months of Capacity w/ 512MB CF** |
Months of Capacity w/ 1GB CF*** |
| Model |
Event |
File Size (KB) |
Typical |
Severe |
Typical |
Severe |
Typical |
Severe |
Typical |
Severe |
| PX-4000 |
Sub-Cycle Disturbance |
483 |
10 |
60 |
4.7 |
28.3 |
100 |
17 |
209 |
35 |
| PX-6000 |
ITIC Event |
483 |
5 |
20 |
2.4 |
9.4 |
200 |
50 |
417 |
104 |
| |
Sub-Cycle Disturbance |
483 |
10 |
60 |
4.7 |
28.3 |
100 |
17 |
209 |
35 |
| |
ITIC and Sub-Cycle Disturbance |
Total |
15 |
80 |
11.8 |
66.0 |
40 |
7 |
83 |
15 |
| PX-8000 |
ITIC Event |
483 |
5 |
20 |
2.4 |
9.4 |
200 |
50 |
417 |
104 |
| |
Sub-Cycle Disturbance |
483 |
10 |
60 |
4.7 |
28.3 |
100 |
17 |
209 |
35 |
| |
Transients |
2048 |
3 |
30 |
6.0 |
60.0 |
79 |
8 |
164 |
16 |
| |
ITIC, Sub-Cycle and Transients combined |
Total |
18 |
110 |
13.1 |
95.2 |
36 |
5 |
75 |
10 |
*The typical and severe power quality event occurrences are estimates and my vary depending on the electrical Environment.
**With 512 MB optional CompactFlash Card; memory is not allocated by event category; memory is used first come, first served.
***With 1 GB optional CompactFlash Card; memory is not allocated by event category; memory is used first come, first served.
Built-in ITIC performance curve analysis - Takes the guesswork out of understanding the severity of IT power quality events
The ITIC (Information Technology Industry Council) curve describes how much (or how little) voltage your IT equipment can sustain without
damage, over what length of time (nanoseconds to seconds). When you can plot power events in this broader context—relative to multiple
variables—you can identify trouble that could cause damage or may be brewing. Of the few meters that can plot events on an ITIC curve,
most require special software to do it. Eaton's Power Xpert 4000/6000/8000 meters require no special software. Right out of the box, these
meters populate and display ITIC curves on both the local display and the Web interface.
ITIC curves
The Power Xpert 6000 and 8000 meter models automatically plot
events on the ITIC curve. The user can drill down on any specific
event and get information on where exactly the event hit and what
was its magnitude and duration. With the optional Power Xpert
Network Time Server, all events get time stamped at a 1 millisecond
synchronized resolution.
The ITIC Web page includes counters
to track the occurrence of disturbances
and a pass/fail summary.
In addition, selecting any disturbance
counter links to a detailed
event view of the disturbances in
that ITIC category. Disturbance
waveforms can be viewed from
the browser.