Powerware
9 Prestige

Specification
Details
High
voltage details
|
Electrical
|
|
Allowable
Input Range
(without using batteries)
|
600-1800
VA: 140-276 VAC
3000 VA: 160-276 VAC
3000 VA (rack): 176-276 VAC
4500/6000: 176-276 VAC |
|
Input
Power Factor
|
.90
typical @ full load |
|
Surge
Protection
|
per
EN 50082-1, tested to IEC 801-4, IEEE 587 |
|
Output
Waveform
|
Sine
wave |
|
Output
Regulation
|
+/-3% |
|
Output
Voltage THD
|
600-1800
VA: <5%, 100% non-linear load
2500-6000 VA: <3%, linear load |
|
Load
Crest Ratio
|
3:1 |
|
Common
Mode Noise Rejection
|
>60dB |
|
Transverse
Mode Noise Rejection
|
>80dB |
| Battery |
|
Battery
type
|
Sealed,
lead-acid; maintenance free |
|
Recharge
Time
|
600-1800
VA: 8 hours to 80% capacity
3000-6000 VA: 6 hours to 90% capacity
3000 VA (rack): 4 hours to 90% capacity (2 battery trays) |
|
Diagnostics
|
Automatic
on-line test without exposing the load |
|
Optional
Battery Pack Weight (cabinet models)
|
Full
pack: 52 lb/23.6 kg
Half pack (800-1800 EXT only): 29.5 lb/13.4 kg |
|
Optional
Battery Pack (cabinet models;
H x W X D)
|
5.6x9.9x15.8
in/
14.3x25.2x40.0 cm> |
| General |
|
Architecture
|
True
online, double-conversion, powerline isolated |
|
User
Interface
|
5
segment LED display with meters and alarms |
|
Operation
|
Fully
automatic, touch-pad control |
|
Diagnostics
|
Full
system self-test on power up |
|
UPS
Bypass
|
Automatic
on overload or UPS failure |
|
Replacement
Electronics (cabinet models)
|
600-1800
VA: Hot-swappable via PowerPass Maintenance bypass module |
|
Battery
Service
|
Hot-swappable,
external battery packs
3000 VA rack: hotpluggable battery trays (2 trays standard
with unit) |
|
Communications
|
RS-232,
LAN contacts, AS/400, Novell, 3 COM |
|
Networks
|
Connectivity
via Ethernet & Token Ring SNMP Adapter |
|
Safety
|
UL
1778, CSA-C22.2 No. 107.1; CE certification |
| Environmental |
|
Audible
Noise
|
600-1800
VA: 45dBA @ 1 meter
3000-6000 VA: 50dBA @ 1 meter |
|
Ambient
Operating Temperature
|
10
to 40C (50 to 104F) |
|
Ambient
Storage Temperature
|
-20
to 60C (-4 to 140F) |
|
Relative
Humidity
|
5-95%
non-condensing |
|
EMI
Suppression
|
600-1800
VA: EN50081-1 EN50082-1
3000-6000 VA: FCC Part 15, sub part J Class A; CISPR Class
A |
|
Packaging
|
No
CFCs, recyclable |
High voltage model
selection guide
| Model1 |
Input
Voltage (VAC)2 |
Output
Voltage (VAC) |
Frequency
(Hz) |
Input
Connection3 |
Output
Connections |
Output
Current (Amp) |
Dimensions
HxWxD (cm) |
Unit
Weight (kg/lb) |
| 600 - 1800 VA Models |
| 600VA/420W |
208
- 240 |
208
- 240 |
45
- 65 |
IEC-320,
10 A |
(3)IEC-320 |
2.64 |
14.3
x 25.2 x 40.0 |
12.9/28.55 |
| 800VA/560W |
208
- 240 |
208
- 240 |
45
- 65 |
IEC-320,
10 A |
(3)IEC-320 |
3.54 |
14.3
x 25.2 x 40.0 |
12.9/28.55 |
| 1000VA/700W |
208
- 240 |
208
- 240 |
45
- 65 |
IEC-320,
10 A |
(3)IEC-320 |
4.34 |
14.3
x 25.2 x 40.0 |
12.9/28.55 |
| 800VA/560W
EXT |
208
- 240 |
208
- 240 |
45
- 65 |
IEC-320,
10 A |
(3)IEC-320 |
3.54 |
14.3
x 25.2 x 40.0 |
14.9/33.05 |
| 1000VA/700W
EXT |
208
- 240 |
208
- 240 |
45
- 65 |
IEC-320,
10 A |
(3)IEC-320 |
4.34 |
14.3
x 25.2 x 40.0 |
14.9/33.05 |
| 1250VA/875W
EXT |
208
- 240 |
208
- 240 |
45
- 65 |
IEC-320,
10 A |
(3)IEC-320 |
5.44 |
14.3
x 25.2 x 40.0 |
14.9/33.05 |
| 1500VA/1050W
EXT |
208
- 240 |
208
- 240 |
45
- 65 |
IEC-320,
10 A |
(3)IEC-320 |
6.54 |
14.3
x 25.2 x 40.0 |
14.9/33.05 |
| 1800VA/1200W
EXT |
208
- 240 |
208
- 240 |
45
- 65 |
IEC-320,
16 A |
(3)IEC-320 |
7.84 |
14.3
x 25.2 x 40.0 |
14.9/33.05 |
| 2500 - 6000 VA Models |
| 2500VA/1750W |
200
- 240 |
200
- 240 |
45
- 65 |
IEC-320,
16 A |
(1)IEC-320,
16 A6 |
10.47 |
25.6
x 25.2 x x40.08 |
31.1/68.58 |
| 3000VA/2100W |
200
- 240 |
200
- 240 |
45
- 65 |
IEC-320,
16 A |
(1)IEC-320,
16 A6 |
12.57 |
25.6
x 25.2 x x40.08 |
31.1/68.58 |
| 3000VA/21000W
(rack) |
200
- 240 |
200
- 240 |
45
- 65 |
IEC-320,
16 A |
(2)IEC-320,
10 & 16 A6 |
12.547 |
17.7
x 43.2 x x61.08 |
54.5/120.08 |
| 4500VA/3000W |
200
- 240 |
200
- 240 |
45
- 65 |
L6-30P
or Hardwired |
L6-30P
or Hardwired |
19.07 |
42.7
x 25.2 x x40.08 |
64.2/143.09 |
| 6000VA/4000W |
200
- 240 |
200
- 240 |
45
- 65 |
L6-30P
or Hardwired |
L6-30P
or Hardwired |
25.07 |
42.7
x 25.2 x x40.08 |
64.2/143.09 |
1EXT
Models and 2500 - 6000VA models accommodate additional battery
packs.
2200 (models above 1800 VA only),
208, 220, 230, and 240 VAC, nominal voltage.
3Includes 6-foot (2 meter) detachable line cord
with region-specific plug, except hardwired models.
4Based on 230 VAC.
5With standard, internal battery.
6Or optional output strip with (6) IEC, British,
Schuko (European), French, or Australian receptacles.
7Based on 240 VAC.
8With UPS electronics and battery pack stacked.
9With UPS electronics and two standard battery
packs.
600 High voltage battery
run times (in minutes)
Note: More battery run times below
Load
(VA)
at 0.7 pf* |
Load
(W) |
600 |
800 |
1000 |
800
EXT |
1000
EXT |
1250
EXT |
| 200 |
140 |
33 |
33 |
33 |
56 |
56 |
56 |
| 400 |
280 |
21 |
21 |
21 |
29 |
29 |
29 |
| 600 |
420 |
11 |
11 |
11 |
19 |
19 |
19 |
| 800 |
560 |
- |
7 |
7 |
13 |
13 |
13 |
| 1000 |
700 |
|
|
6 |
|
10 |
10 |
| 1250 |
875 |
- |
- |
- |
- |
- |
8 |
External Battery Cabinet Configurations (600
- 12500 VA High Voltage EXT Models)
| Load
(VA) at 0.7 pf* |
Load
(W) |
1/2
Cabinet |
1
Cabinet |
1-1/2
Cabinet |
2
Cabinet |
2-1.2
Cabinet |
3
Cabinet |
3-1/2
Cabinet |
4
Cabinet |
| 200 |
140 |
133 |
203 |
274 |
346 |
418 |
491 |
564 |
637 |
| 400 |
280 |
70 |
117 |
159 |
201 |
243 |
295 |
328 |
371 |
| 600 |
420 |
46 |
76 |
110 |
141 |
171 |
200 |
230 |
260 |
| 800 |
560 |
33 |
55 |
79 |
105 |
132 |
153 |
176 |
199 |
| 1000 |
700 |
25 |
42 |
61 |
81 |
102 |
124 |
147 |
161 |
| 1250 |
875 |
19 |
32 |
46 |
61 |
77 |
94 |
111 |
129 |
*Typical Power factor
(PF)
1500 High voltage battery run times (in minutes)
| Load
(VA) at 0.7 pf* |
Load
(W) |
Int
UPS
Batt |
½
Cab |
1
Cab |
1
½ Cab |
2
Cab |
2
½ Cab |
3
Cab |
3
½ Cab |
4
Cab |
| 200 |
140 |
59 |
128 |
194 |
260 |
327 |
393 |
460 |
527 |
595 |
| 400 |
280 |
29 |
64 |
107 |
149 |
186 |
224 |
263 |
302 |
339 |
| 600 |
420 |
19 |
42 |
71 |
102 |
135 |
161 |
189 |
217 |
244 |
| 800 |
650 |
14 |
32 |
52 |
76 |
100 |
125 |
148 |
169 |
191 |
| 1000 |
700 |
11 |
24 |
41 |
59 |
77 |
98 |
119 |
138 |
156 |
| 1250 |
900 |
8 |
19 |
32 |
45 |
59 |
76 |
92 |
108 |
125 |
| 1500 |
1000 |
7 |
14 |
25 |
36 |
48 |
60 |
73 |
86 |
101 |
| 1800 |
1200 |
5 |
12 |
20 |
29 |
38 |
48 |
59 |
69 |
80 |
*Typical
Power factor (PF)
3000 High voltage battery run times (in minutes)
| Load
(VA) at 0.7 pf* |
1
Cab |
2
Cab |
3
Cab |
| 600 |
36.8 |
88 |
146 |
| 800 |
27.6 |
66 |
110 |
| 1200 |
18.4 |
44 |
73 |
| 1600 |
13.6 |
33 |
54 |
| 2000 |
10.7 |
26 |
42 |
| 2500 |
8.3 |
20 |
33 |
| 3000 |
6.5 |
16 |
27 |
6000 High voltage battery run times (in minutes)
Load
(VA) |
Load
(W) |
2
Packs |
3
Packs |
4
Packs |
5
Packs |
6
Packs |
| 1500 |
1000 |
30 |
44 |
58 |
72 |
87 |
| 3000 |
2000 |
14 |
24 |
32 |
39 |
47 |
| 4500 |
3000 |
7 |
14 |
22 |
27 |
32 |
| 6000 |
4000 |
5 |
9 |
14 |
21 |
25 |
This
guide provides typical application information. Battery times
are approximate and may vary with equipment, configuration,