Powerware
9 Prestige

Specification
Details
Low
voltage details
| Electrical |
|
Allowable
Input Range
(without using batteries)
|
650-2000
VA: 85-144 VAC (full load); 75-144 (half load)
3000 VA; 120 V: 90-144 VAC
3000 VA; 230 V: 160-276 VAC
4500/6000: 170-276 VAC |
|
Input
Power Factor
|
650-2000
VA: .95 typical @ full load
3000-6000 VA: .90 typical @full load |
|
Surge
Protection
|
120
volt input models: Tested to IEEE 587/ANSI C62.41 Categories
A & B
230 volt input models: per EN 50082-1, meets IEC 801-4,
IEEE 587 |
|
Output
Waveform
|
Sine
wave |
|
Output
Regulation
|
+/-3% |
|
Output
Voltage THD
|
650-2000
VA: <5%, 100% non-linear load
3000-6000 VA: <3%, linear load |
|
Load
Crest Ratio
|
3:1 |
|
Common
Mode Noise Rejection
|
>60dB |
|
Transverse
Mode Noise Rejection
|
>80dB |
| Mechanical |
|
Optional
Battery Pack Weight
|
Full
pack: 52 lb/23.6 kg
Half pack (1000-2000 EXT models only): 29.5 lb/13.4 kg |
|
Optional
Battery Pack Dimensions (H x W x D)
|
5.6x9.9x15.8
in/
14.3x25.2x40.0 cm |
| Battery |
|
Battery
type
|
Sealed,
lead-acid; maintenance free |
|
Recharge
Time
|
650-2000
VA: 4 hours to 80% capacity
3000-6000 VA: 6 hours to 90% capacity |
|
Diagnostics
|
Automatic
on-line test without exposing the load |
| General |
|
Architecture
|
True
online, double-conversion, powerline isolated |
|
Diagnostics
|
Full
system self-test on power up |
|
UPS
Bypass
|
Automatic
on overload or UPS failure |
|
Replacement
Modules
|
Hot-swappable
external battery packs and electronics via PowerPass Maintenance
bypass module |
|
Communications
|
RS-232,
LAN contacts, AS/400, Novell, 3 COM |
|
Networks
|
Connectivity
via Ethernet & Token Ring SNMP Adapter |
|
Safety
|
All
models: UL 1778, CSA-C22.2 No. 107.1;EN 50091-1 for all
models except 3000 VA, 120 V; 4500/600 VA: also EN60950 |
| Environmental |
|
Audible
Noise
|
650-2000
VA: 45dBA @ 1 meter
3000-6000 VA: 50dBA @ 1 meter |
|
Ambient
Operating Temperature
|
10
to 40oC (50 to 104oF) |
|
Ambient
Storage Temperature
|
-20
to 60oC (-4 to 140oF) |
|
Relative
Humidity
|
5-95%
non-condensing |
|
EMI
Suppression
|
All
models: FCC Part 15, sub part J Class A; Class B available
on selected models - 2kVA, 230 volt input models: also
CISPR Class A |
|
Packaging
|
No
CFCs, recyclable |
Low voltage model
selection guide
| Model1 |
Input
Voltage (VAC) |
Output
Voltage (VAC) |
Frequency
(Hz) |
Input
Connection2 |
Output
Connections |
Output
Current (Amp) |
Dimensions
HxWxD (cm) |
Unit
Weight (lb/kg) |
|
650 - 3000 VA Models |
| 650VA/445W |
120 |
120 |
45
- 65 |
5-15P |
(4)5-15R |
5.4 |
5.6
x 9.9 x 15.8 |
28.5/12.93 |
| 800VA/560W |
120 |
120 |
45
- 65 |
5-15P |
(4)5-15R |
6.7 |
5.6
x 9.9 x 15.8 |
28.5/12.93 |
| 1000VA/700W |
120 |
120 |
45
- 65 |
5-15P |
(4)5-15R |
8.3 |
5.6
x 9.9 x 15.8 |
28.5/12.93 |
| 750VA/525W
EXT |
120 |
120 |
45
- 65 |
5-15P |
(4)5-15R |
6.3 |
5.6
x 9.9 x 15.8 |
28.5/12.93 |
| 1000VA/700W
EXT |
120 |
120 |
45
- 65 |
5-15P |
(4)5-15R |
8.3 |
5.6
x 9.9 x 15.8 |
33.0/14.93 |
| 1250VA/875W
EXT |
120 |
120 |
45
- 65 |
5-15P |
(4)5-15R |
10.4 |
5.6
x 9.9 x 15.8 |
33.0/14.93 |
| 1500VA/1050W
EXT |
120 |
120 |
45
- 65 |
5-15P |
(4)5-15R |
12.5 |
5.6
x 9.9 x 15.8 |
33.0/14.93 |
| 2000VA/1300W
EXT |
120 |
120 |
45
- 65 |
5-20P |
(4)5-15R
& (1) 5-20R |
16.0 |
5.6
x 9.9 x 15.8 |
33.0/14.93 |
| 3000VA/2100W |
120 |
120 |
45
- 65 |
L5-30P |
(1)5-15R
& (1) L5-30R |
25.5 |
11.2
x 9.9 x 15.84 |
68.5/31.14 |
| 2500
- 6000 VA Models with PowerPass Module |
| 2500VA/1750W |
200
- 2405 |
120/208,
120/240 |
45
- 65 |
IEC-320,
16 A |
|
10.46 |
16.8
x 9.9 x 15.87 |
115.5/52.57 |
| 3000VA/2000W |
200
- 2405 |
120/208,
120/240 |
45
- 65 |
IEC-320,
16 A |
|
12.56 |
16.8
x 9.9 x 15.87 |
115.5/52.57 |
| 4500VA/3000W6 |
200
- 2405 |
120/208,
120/240 |
45
- 65 |
L6-30P
or Hardwired |
|
19.06 |
33.6
x 9.9 x 15.88 |
218.0/98.98 |
| 6000VA/4000W6 |
200
- 2405 |
120/208,
120/240 |
45
- 65 |
L6-30P
or Hardwired |
|
25.06 |
33.6
x 9.9 x 15.88 |
218.0/98.98 |
1EXT
Models and 2500 - 6000VA models accommodate additional battery
packs.
2Includes 6-foot (2 meter) detachable line cord
with region-specific plug, except hardwired models.
3With standard, internal battery.
4With UPS electronics an done battery pack stacked.
5200, 208, 220, 230, or 240 VAC.
6Based on 240 VAC.
8With UPS electronics, battery pack, and PowerPass
stacked.
9With UPS electronics, two standard battery packs,
and PowerPass stacked.
650 Low voltage battery
run times (in minutes)
(Note: more battery run times below)
Load
(VA)
at 0.7 pf* |
Load
(W) |
650 |
800 |
1000 |
750
EXT |
1000
EXT |
1250
EXT |
1500
EXT |
| 200 |
140 |
37 |
37 |
37 |
68 |
68 |
68 |
68 |
| 400 |
280 |
22 |
22 |
22 |
32 |
32 |
32 |
32 |
| 600 |
420 |
12 |
12 |
12 |
20 |
20 |
20 |
20 |
| 800 |
560 |
- |
8 |
8 |
15** |
14 |
14 |
14 |
| 1000 |
700 |
- |
- |
6 |
- |
11 |
11 |
11 |
| 1250 |
875 |
- |
- |
- |
- |
- |
8 |
8 |
| 1500 |
1050 |
- |
- |
- |
- |
- |
- |
6 |
**750VA,
525W
External Battery Cabinet Configurations (650 - 1500
VA Low Voltage EXT Models)
| Load
(VA) at 0.7 pf* |
Load
(W) |
1/2
Cabinet |
1
Cabinet |
1-1/2
Cabinet |
2
Cabinet |
2-1.2
Cabinet |
3
Cabinet |
3-1/2
Cabinet |
4
Cabinet |
| 200 |
140 |
143 |
216 |
290 |
364 |
438 |
513 |
589 |
663 |
| 400 |
280 |
69 |
115 |
158 |
198 |
239 |
280 |
320 |
362 |
| 600 |
420 |
43 |
73 |
105 |
137 |
165 |
194 |
221 |
249 |
| 800 |
560 |
33 |
56 |
80 |
106 |
134 |
156 |
178 |
202 |
| 1000 |
700 |
23 |
39 |
57 |
75 |
95 |
114 |
135 |
151 |
| 1250 |
875 |
17 |
30 |
42 |
56 |
70 |
86 |
102 |
118 |
| 1500 |
1050 |
14 |
23 |
32 |
43 |
55 |
67 |
78 |
91 |
*Typical
Power factor (PF)
2000 Low voltage battery
run times (in
minutes)
Load
(VA)
at 0.7 pf* |
Load
(W) |
Internal
UPS
Battery |
½
Cab |
1
Cab |
1
½
Cab |
2
Cab |
2
½
Cab |
3
Cab |
3
½
Cab |
4
Cab |
| 200 |
140 |
72 |
150 |
228 |
306 |
384 |
463 |
542 |
620 |
700 |
| 400 |
280 |
34 |
74 |
122 |
166 |
209 |
251 |
294 |
337 |
380 |
| 600 |
420 |
22 |
47 |
78 |
113 |
145 |
175 |
204 |
235 |
265 |
| 800 |
650 |
15 |
33 |
56 |
81 |
107 |
135 |
157 |
179 |
203 |
| 1000 |
700 |
12 |
25 |
43 |
61 |
82 |
103 |
125 |
144 |
162 |
| 1250 |
900 |
9 |
19 |
32 |
47 |
61 |
77 |
95 |
112 |
130 |
| 1500 |
1000 |
7 |
15 |
25 |
37 |
49 |
61 |
74 |
88 |
102 |
| 2000 |
1300 |
5 |
10 |
17 |
24 |
32 |
41 |
50 |
59 |
69 |
*Typical
Power factor (PF)
3000 Low voltage battery
run times (in
minutes)
| Load
(VA) |
Load
(W) |
1
Pack |
2
Packs |
3
Packs |
| 400 |
280 |
72 |
150 |
227 |
| 800 |
560 |
36 |
79 |
122 |
| 1200 |
840 |
23 |
53 |
82 |
| 1600 |
1100 |
16 |
38 |
61 |
| 2000 |
1400 |
12 |
30 |
48 |
| 2500 |
1750 |
8 |
23 |
37 |
| 3000 |
2100 |
6.5 |
17 |
29 |
This
guide provides typical application information. Battery times
are approximate and may vary with equipment, configuration,
disk access, battery age, temperature, etc.
|