Powerware
9 Prestige

Specification
Details
Rack-mount
details
| 200
- 240 VAC |
| Electrical |
| Input
Voltage |
200,
208, 220, 230, 240 VAC Nominal |
| Allowable
Range |
176-276
VAC without batteries |
| Input
Frequency |
45-65
Hz
|
| Input
Power Factor |
.90
Typical at full load and nominal use |
| Surge
Protection |
per
EN50082-1 tested to IEC 801-4, IEEE587 |
| Output
Voltage |
200,
208, 220, 230, 240 VAC +/- 3% (user-selectable) |
|
Output
Ratings
|
3000
VA / 2100 W
|
| Output
Current |
15A
/ 200VAC
14.4A / 208VAC
13.6A / 220VAC
13A / 230VAC
12.5A / 240VAC |
| Output
Voltage THD |
<3%
Linear load, <5% Non-linear load |
| Load
Crest Ratio |
3:1 |
| Common
Mode Noise Rejection |
>60
dB |
| Transverse
Mode Noise Rejection |
>80
dB |
| Physical |
| UPS
weight with standard battery |
54.5
kg / 120 lbs.
|
| UPS
Dimensions |
177mm
H x 432mm W x 610mm D
6.97"h x 17"w x 24"d
|
| Battery |
| Battery
Type |
Sealed,
lead-acid/maintenance free
|
| Full
Load Support Time |
7
minutes (2 battery trays) |
| Recharge
time |
4
hours to 90% capacity (2 battery trays) |
| Diagnostics |
Automatic
on-line test without exposing load
|
| General |
| Architecture |
On-line,
double-conversion, powerline isolated |
| User
Interface |
5
segment LED display with meters and alarms
|
| Operation |
Fully
automatic, touch-pad control |
| Diagnostics |
Full
system self test on power up
|
| UPS
Bypass |
Automatic
on overload or UPS failure |
| Battery
Servicing |
Hot
pluggable battery trays (2 trays standard with unit) |
| Communications |
RS-232,
LAN contacts, AS/400, Novell, 3Com, Banyan
|
| Networks |
Connectivity
via Ethernet & Token Ring SNMP Adapter |
| Input |
Detachable
2 meter (6') line cord with region-specific plug
|
| Output |
(1)
IEC 320, 16A receptacle and
(1) IEC 320, 10A receptacle |
| Safety |
UL
1778, CSA-C22.2 No. 107.1, CE Certification |
| Environmental
and safety |
| Audible
Noise |
<50
dBA typical
|
| Ambient
Operating Temperature |
+10C
to +40C
|
| Ambient
Storage Temperature |
-20C
to +60C
|
| Relative
Humidity |
5-95%,
non-condensing
|
| Altitude |
4000
feet with derating
|
| EMI
Suppression |
FCC
Part 15, Subpart J Class A, CISPR A
|
| Packaging |
No
CFC's, Recyclable
|
*Specifications
subject to change without notice.
Rack-mount battery run times (in
minutes)
Load
(VA) |
Load
(W) |
Two
Battery Trays |
| 400 |
280 |
72 |
| 800 |
560 |
36 |
| 1200 |
840 |
23 |
| 1600 |
1100 |
16 |
| 2000 |
1400 |
12 |
| 2500 |
1750 |
8 |
| 3000 |
2100 |
6.5 |
This guide provides typical application information.
Battery times are approximate and may vary with equipment,
configuration, disk access, battery age, temperature, etc.
|