Bomara Associates Logo
Eaton Authorized Power Specialist
Loading
Bomara Associates Homepage

Eaton EX RT UPS


pulsar EX RT


Versatile form factor
The Eaton® EX RT UPS is a UPS designed for sensitive high-density server environments and harsh industrial applications. Specifically engineered to meet demanding customer applications in IT systems, measuring instruments, PLCs and industrial PC markets, the EX RT is fully compatible with genset redundancy requirements in most instances. The manual bypass, hot-swap I/O box and intuitive LCD control panel are just a few of the many differentiating features that make the EX RT the ideal product for the 5–11 kVA power range.

(Full specifcations)

High reliability and availability

  • Internal static bypass
  • Input/output (I/O) box with manual bypass

Industrial grade performance

  • Large input voltage range without using battery power
  • 40–70 Hz input frequency range
  • Operating temperature: 0°–40°C permanently, 0°–45°C for eight hours
  • Standalone solution with modular design for industrial needs

Optimized solution for infrastructure network integration

  • Rack kit for an optimized mounting with 3U height per module
  • Communications slot compatible with multiple communication card protocols
  • Software application packages are fully customized
  • Long backup time availability—up to 8 hours and UL924 listed solutions

Services

  • Warranty: Two years, parts and labor (US and Canada)
  • On-site services available for startup, preventive maintenance and more
  • Extended warranty contracts: Warranty+ 1, Warranty+ 3

The solution for high-density rack server enclosures and industrial environments

  • Hot-swap battery and UPS modules prevent interruptions
  • Internal and maintenance bypass are standard to achieve the highest level of availability
  • Large input voltage window without using battery power
  • Automatic battery test and protection against deep discharges

PULSAR EX RT

Compatibility with any environment Data room

  • Versatile rack or tower in 6U, including the power and battery modules
  • Management through various protocols such as HTTP/SNMP/ XML/Telnet
  • Integration with popular network management systems like HP Openview, IBM Tivoli, CA Unicenter
  • Integrated NEMA receptacles included with transformer configuration
  • Optional rackmount PDU with NEMA or IEC sockets to facilitate power distribution within the enclosure

Ergonomics

  • Multilingual scrolling LCD front bezel control panel
  • Simple setup on network or industrial mode permits system shutdown or service continuity in case of overload or short circuit
  • Event log for easy fault detection

Battery backup

  • Battery modules up to eight hours with the CLA* charger module
  • Space saving battery connector cables and extra long battery cables for separate battery racks
  • Battery detection system automatically configures battery modules and UPS
  • UL 924 emergency lighting and equipment battery cabinets available (90-minute runtime)
  • *CLA for external battery cabinet only

High-end ergonomics

  • Versatile 6U rack or tower design
  • Multilingual LCD
  • Two stands improve stability of the tower
  • Up to five extra battery modules to extend runtime up to two hours
  • Voltage-free contacts are included for remote status monitoring

Industry and infrastructure

  • Battery integration system optimizes the footprint of extended
    runtime solutions with automatic battery module detection
  • Genset compatibility
  • Integration with building management systems (Jbus), six voltage-free contacts for remote status monitoring
  • Temperature and humidity supervision with an environment sensor triggers an orderly shutdown

Large choice of options to meet customer needs

  • Universal 3U transformer module: System earth arrangement, galvanic isolation for upstream and downstream UPS installation
  • Battery integration system for optimized footprint: up to eight modules stacked on a caster kit—one UPS module, six EXB battery modules and one transformer module
  • 3U CLA module for backup times up to eight hours

User-friendly installation and operation

  • Load metering in kW/kVA is permanently displayed on the LCD
  • Operating mode, battery capacity in percentage, voltage measurement, normal AC, bypass (separate AC) input/output, serial number and power rating identification are available by scrolling up or down
  • Event logs and fault diagnostics facilitate maintenance and repair

Full customization through a configuration panel in Personal Solution-Pac

  • CLA, hot standby, ECO mode, frequency converter setup
  • Low battery, battery test frequency, disable deep discharge protection
  • AC bypass input tolerance settings for: frequency, voltage-AC bypass transfer condition

images2

 

 

 

 

 

 

 

 

Communications software and connectivity

  • Power management suite (included) comes with network-based shutdown software (Windows, Linux, MacOS, VMware ESX, Microsoft Hyper-V) and local or remote supervision up to five nodes
  • Network Management Card (NMC) connects the UPS to an Ethernet 10/100 network, raising SNMP or XML alarms and supervising the UPS using a simple browser interface
  • NMC environment sensor monitors the temperature, humidity and two relay contacts via SNMP or HTML
  • Enterprise Power Manager supervisor provides comprehensive management of multiple UPSs and PDUs using a Windows PC (vendor neutral)
  • NMS integration kits include HP OpenView, IBM Tivoli Netview, CA Unicenter, etc.
  • Status information card monitors for voltage-free contacts and Remote Power Off (RPO) function
  • NetWatch 5.0 software automatically shuts down UPS-protected devices, such as servers

EX RT Back Panel (Transformer Module/Power Module/Battery Module)
Text Box:

X R\T Back Panel (Battery Module /Power Module)


text box 4
  • Slot for communication cards
  • Output contracts communication port
  • Remote Emergency Power Off communication port (REPO)
  • Connectors for automatic detection of battery modules
  • RS232 communication port
  • Battery module connectors
  • to the UPS or the battery modules)
  • Manual bypass switch
  • Output terminal block
  • Normal AC source switch10 Normal AC source terminal block 11 Bypass AC source terminal block 12 Battery circuit-breaker

Eaton customer service and support

  • Flex and PowerTrust on-site services from factory-trained personnel for startup, preventive maintenance and more
  • Extended warranty contracts Warranty + 1

Warranty + 3

  • UPSgradeTM program for substitution of an old UPS (vendor neutral), includes the EX RT 5 kVA model

EX RT BATTERY BACKUP TIMES (In MINUTES)*


Load (VA/Watts)

Internal
Batteries

+1 EBM

+2 EBMs

+3 EBMs

+4 EBMs

+5 EBMs

EX RT 5000

 

 

 

 

 

 

500/400

170

358

540

740

892

1220

1000/800

91

170

260

355

505

540

1500/1200

49

110

170

240

290

355

2000/1600

33

84

120

170

235

260

2500/2000

25

60

100

122

170

225

3000/2400

21

46

75

110

135

170

3500/2800

16

39

64

95

119

140

4000/3200

13

31

57

84

105

120

4500/3600

11

27

52

68

92

110

5000/4000

9

25

45

60

84

100

EX RT 7000

 

 

 

 

 

 

700/490

121

266

447

578

756

889

1400/890

57

125

203

244

364

453

2100/1470

37

80

124

185

245

287

2800/1960

28

61

101

128

169

232

3500/2450

21

53

83

108

132

164

4200/2940

15

37

66

90

110

133

4900/3430

12

30

55

75

98

118

5600/3920

10

24

45

61

77

102

6300/4410

8

22

38

53

69

86

7000/4900

7

20

32

45

57

72

EX RT 11000

 

 

 

 

 

 

1100/800

90

191

293

392

525

637

2200/1600

40

93

143

199

261

312

3300/2400

25

61

96

135

172

201

4400/3200

18

43

71

99

120

142

5500/4000

14

30

53

84

102

113

6600/4800

11

24

44

60

86

102

7700/5600

9

20

34

51

67

87

8800/6400

7

17

27

43

56

68

9900/7200

6

15

24

35

48

60

11000/8000

5

14

22

30

42

53

Technical specifications

PERFORMANCES

Nominal Input Voltage                                  

120–280V at <70% rated output

Input Voltage Range                                    

156–280V at 100% rated output


Input Frequency Range            

40–70 Hz, frequency converter as a standard


Output Voltage/Frequency                          

200/2082/220/230/240/250V; 120V output voltage available with transformer; 50/60 Hz autoselect

Overall Efficiency (Online)                        

90–97%/<5%

Mode–ECO Mode)/Harmonic


Current Distortion

Crest Factor/Overload Capacity 3:1 / 2 min if 102%<overload<110%, 1 min if 110%<overload<125%, 30 sec if 125%<over load<150%, 500 msec if overload >150%

 


Operating Temperature                              

45°C for 8 hr, 0°–40°C continuous

CONNECTION

Block Power Module

Input/Output Terminal Block               

Hardwired


Maximum Wire Size                                       

5/7 kVA: 10 mm/6 AWG

(Solid or Stranded Wire)                             

11 kVA: 13 mm/4 AWG


Step-Down Transformer                           

120/208/240 Vac output

Output Configuration                                      

Terminal block, plus (2) NEMA L6-30R (208V), (8

NEMA 5-20R; optional PDUs for additional NEMA or IEC receptacles


COMMUNICATION

Port Type                                        

(6) voltage-free dry contacts DB-9 rated at 2A 48V DC, (1) RS 232, (1) RJ11 for RPO (Remote Power Off)


Slot                                                   

(1) slot for Mini-Slot communication card

[Network Management Card (SNMP/Web), NMC
ModBus/JBus, MC Contacts/Serial]


STANDARD AND CERTIFICATION

Performance and Safety

IEC 62040-1/CEI 60950/UL 1778 and CSA 22.2 Standards

EMC                                            

IEC 62040-2; EN 50091-2; FCC class A

WARRANTY                

Two years, parts and labor (US and Canada)

  1. Due to continuing product improvement programs, specifications are subject to change without notice
  2. Default voltage
  3. Configurable to daily or monthly

EX RT INDIVIDUAL MODULES AND OPTIONS


Part Number and Description

5 kVA/4 kW

7 kVA/4.9 kW

11 kVA/8 kW

EX RT Power and Battery Modules

 

 

 

Power Module with rails

86215

86216

86217

Battery Module with rails

86207

86207

86209

UL924 Battery Module

86218

86219

86220

EX RT Transformer

 

 

 

7 kVA Transformer with rails

 

86311

 

11 kVA Transformer with rails

 

 

86211

EX RT CLA Charger Module

 

 

 

CLA Charger with rails

86214

86214

86214

Battery Integration Kit with Casters

 

 

 

Stack kit with inter-module fastening, swivel wheels, brakes, leveling feet

86005

86005

86005

EX RT INDIVIDUAL MODULES AND OPTIONS

Part Number and Description

5 kVA/4 kW

7 kVA/4.9 kW

11 kVA/8 kW

EX RT Power and Battery Modules

 

 

 

Power Module with rails

86215

86216

86217

Battery Module with rails

86207

86207

86209

UL924 Battery Module

86218

86219

86220

EX RT Transformer

 

 

 

7 kVA Transformer with rails

 

86311

 

11 kVA Transformer with rails

 

 

86211

EX RT CLA Charger Module

 

 

 

CLA Charger with rails

86214

86214

86214

Battery Integration Kit with Casters

 

 

 

Stack kit with inter-module fastening, swivel wheels, brakes, leveling feet

86005

86005

86005

Ordering Information: EX RT MODELS

Catalog
Number

Style Number

Form Factor

Rating (VA/Watts)

Output Voltage

Input Connection

EXRTG5000-XL6UMS

86505

Rack/Tower

5000/4000

HV

Hardwired

EXRTG7000-XL6UMS

86507

Rack/Tower

7000/4900

HV

Hardwired

EXRTG11000-XL6UMS

86511

Rack/Tower

11000/8000

HV

Hardwired

EXRTL5000-XL9UMS

86506

Rack/Tower

5000/4000

LV

Hardwired

EXRTL7000-XL9UMS

86508

Rack/Tower

7000/4900

LV

Hardwired

EXRTL11000-XL9UMS

86512

Rack/Tower

11000/8000

LV

Hardwired

 


Powerware Home
Bomara Homepage
Request Information

Bomara Associates Phone: 800.5BOMARA (800.526.6272) Phone: 978.452.2299 Fax: 978.452.1169 3 Courthouse Lane, Chelmsford, MA 01824 USA
email: bobr@bomara.com     web: www.bomara.com