Versatile form factor
The Eaton® EX RT UPS is a UPS designed for sensitive high-density server environments and harsh industrial applications. Specifically engineered to meet demanding customer applications in IT systems, measuring instruments, PLCs and industrial PC markets, the EX RT is fully compatible with genset redundancy requirements in most instances. The manual bypass, hot-swap I/O box and intuitive LCD control panel are just a few of the many differentiating features that make the EX RT the ideal product for the 5–11 kVA power range.
(Full specifcations)
High reliability and availability
- Internal static bypass
- Input/output (I/O) box with manual bypass
Industrial grade performance
- Large input voltage range without using battery power
- 40–70 Hz input frequency range
- Operating temperature: 0°–40°C permanently, 0°–45°C for eight hours
- Standalone solution with modular design for industrial needs
Optimized solution for infrastructure network integration
- Rack kit for an optimized mounting with 3U height per module
- Communications slot compatible with multiple communication card protocols
- Software application packages are fully customized
- Long backup time availability—up to 8 hours and UL924 listed solutions
Services
- Warranty: Two years, parts and labor (US and Canada)
- On-site services available for startup, preventive maintenance and more
- Extended warranty contracts: Warranty+ 1, Warranty+ 3
The solution for high-density rack server enclosures and industrial environments
- Hot-swap battery and UPS modules prevent interruptions
- Internal and maintenance bypass are standard to achieve the highest level of availability
- Large input voltage window without using battery power
- Automatic battery test and protection against deep discharges

Compatibility with any environment Data room
- Versatile rack or tower in 6U, including the power and battery modules
- Management through various protocols such as HTTP/SNMP/ XML/Telnet
- Integration with popular network management systems like HP Openview, IBM Tivoli, CA Unicenter
- Integrated NEMA receptacles included with transformer configuration
- Optional rackmount PDU with NEMA or IEC sockets to facilitate power distribution within the enclosure
Ergonomics
- Multilingual scrolling LCD front bezel control panel
- Simple setup on network or industrial mode permits system shutdown or service continuity in case of overload or short circuit
- Event log for easy fault detection
Battery backup
- Battery modules up to eight hours with the CLA* charger module
- Space saving battery connector cables and extra long battery cables for separate battery racks
- Battery detection system automatically configures battery modules and UPS
- UL 924 emergency lighting and equipment battery cabinets available (90-minute runtime)
- *CLA for external battery cabinet only
High-end ergonomics
- Versatile 6U rack or tower design
- Multilingual LCD
- Two stands improve stability of the tower
- Up to five extra battery modules to extend runtime up to two hours
- Voltage-free contacts are included for remote status monitoring
Industry and infrastructure
- Battery integration system optimizes the footprint of extended
runtime solutions with automatic battery module detection
- Genset compatibility
- Integration with building management systems (Jbus), six voltage-free contacts for remote status monitoring
- Temperature and humidity supervision with an environment sensor triggers an orderly shutdown
Large choice of options to meet customer needs
- Universal 3U transformer module: System earth arrangement, galvanic isolation for upstream and downstream UPS installation
- Battery integration system for optimized footprint: up to eight modules stacked on a caster kit—one UPS module, six EXB battery modules and one transformer module
- 3U CLA module for backup times up to eight hours
User-friendly installation and operation
- Load metering in kW/kVA is permanently displayed on the LCD
- Operating mode, battery capacity in percentage, voltage measurement, normal AC, bypass (separate AC) input/output, serial number and power rating identification are available by scrolling up or down
- Event logs and fault diagnostics facilitate maintenance and repair
Full customization through a configuration panel in Personal Solution-Pac
- CLA, hot standby, ECO mode, frequency converter setup
- Low battery, battery test frequency, disable deep discharge protection
- AC bypass input tolerance settings for: frequency, voltage-AC bypass transfer condition

Communications software and connectivity
- Power management suite (included) comes with network-based shutdown software (Windows, Linux, MacOS, VMware ESX, Microsoft Hyper-V) and local or remote supervision up to five nodes
- Network Management Card (NMC) connects the UPS to an Ethernet 10/100 network, raising SNMP or XML alarms and supervising the UPS using a simple browser interface
- NMC environment sensor monitors the temperature, humidity and two relay contacts via SNMP or HTML
- Enterprise Power Manager supervisor provides comprehensive management of multiple UPSs and PDUs using a Windows PC (vendor neutral)
- NMS integration kits include HP OpenView, IBM Tivoli Netview, CA Unicenter, etc.
- Status information card monitors for voltage-free contacts and Remote Power Off (RPO) function
- NetWatch 5.0 software automatically shuts down UPS-protected devices, such as servers
EX RT Back Panel (Transformer Module/Power Module/Battery Module)

X R\T Back Panel (Battery Module /Power Module)
|
- Slot for communication cards
- Output contracts communication port
- Remote Emergency Power Off communication port (REPO)
- Connectors for automatic detection of battery modules
- RS232 communication port
- Battery module connectors
- to the UPS or the battery modules)
- Manual bypass switch
- Output terminal block
- Normal AC source switch10 Normal AC source terminal block
11 Bypass AC source terminal block
12 Battery circuit-breaker
|
Eaton customer service and support
- Flex and PowerTrust on-site services from factory-trained personnel for startup, preventive maintenance and more
- Extended warranty contracts Warranty + 1
Warranty + 3
- UPSgradeTM program for substitution of an old UPS (vendor neutral), includes the EX RT 5 kVA model
EX RT BATTERY BACKUP TIMES (In MINUTES)*
Load (VA/Watts) |
Internal
Batteries |
+1 EBM |
+2 EBMs |
+3 EBMs |
+4 EBMs |
+5 EBMs |
EX RT 5000 |
|
|
|
|
|
|
500/400 |
170 |
358 |
540 |
740 |
892 |
1220 |
1000/800 |
91 |
170 |
260 |
355 |
505 |
540 |
1500/1200 |
49 |
110 |
170 |
240 |
290 |
355 |
2000/1600 |
33 |
84 |
120 |
170 |
235 |
260 |
2500/2000 |
25 |
60 |
100 |
122 |
170 |
225 |
3000/2400 |
21 |
46 |
75 |
110 |
135 |
170 |
3500/2800 |
16 |
39 |
64 |
95 |
119 |
140 |
4000/3200 |
13 |
31 |
57 |
84 |
105 |
120 |
4500/3600 |
11 |
27 |
52 |
68 |
92 |
110 |
5000/4000 |
9 |
25 |
45 |
60 |
84 |
100 |
EX RT 7000 |
|
|
|
|
|
|
700/490 |
121 |
266 |
447 |
578 |
756 |
889 |
1400/890 |
57 |
125 |
203 |
244 |
364 |
453 |
2100/1470 |
37 |
80 |
124 |
185 |
245 |
287 |
2800/1960 |
28 |
61 |
101 |
128 |
169 |
232 |
3500/2450 |
21 |
53 |
83 |
108 |
132 |
164 |
4200/2940 |
15 |
37 |
66 |
90 |
110 |
133 |
4900/3430 |
12 |
30 |
55 |
75 |
98 |
118 |
5600/3920 |
10 |
24 |
45 |
61 |
77 |
102 |
6300/4410 |
8 |
22 |
38 |
53 |
69 |
86 |
7000/4900 |
7 |
20 |
32 |
45 |
57 |
72 |
EX RT 11000 |
|
|
|
|
|
|
1100/800 |
90 |
191 |
293 |
392 |
525 |
637 |
2200/1600 |
40 |
93 |
143 |
199 |
261 |
312 |
3300/2400 |
25 |
61 |
96 |
135 |
172 |
201 |
4400/3200 |
18 |
43 |
71 |
99 |
120 |
142 |
5500/4000 |
14 |
30 |
53 |
84 |
102 |
113 |
6600/4800 |
11 |
24 |
44 |
60 |
86 |
102 |
7700/5600 |
9 |
20 |
34 |
51 |
67 |
87 |
8800/6400 |
7 |
17 |
27 |
43 |
56 |
68 |
9900/7200 |
6 |
15 |
24 |
35 |
48 |
60 |
11000/8000 |
5 |
14 |
22 |
30 |
42 |
53 |
Technical specifications
Nominal Input Voltage
120–280V at <70% rated output
Input Voltage Range
156–280V at 100% rated output
Input Frequency Range
40–70 Hz, frequency converter as a standard
Output Voltage/Frequency
200/2082/220/230/240/250V; 120V output voltage available with transformer; 50/60 Hz autoselect
Overall Efficiency (Online)
Mode–ECO Mode)/Harmonic
Current Distortion
Crest Factor/Overload Capacity 3:1 / 2 min if 102%<overload<110%, 1 min if 110%<overload<125%, 30 sec if 125%<over load<150%, 500 msec if overload >150%
Operating Temperature
45°C for 8 hr, 0°–40°C continuous
Input/Output Terminal Block
Hardwired
Maximum Wire Size
5/7 kVA: 10 mm/6 AWG
(Solid or Stranded Wire)
11 kVA: 13 mm/4 AWG
Step-Down Transformer
120/208/240 Vac output
Output Configuration
Terminal block, plus (2) NEMA L6-30R (208V), (8
NEMA 5-20R; optional PDUs for additional NEMA or IEC receptacles
Port Type
(6) voltage-free dry contacts DB-9 rated at 2A 48V DC, (1) RS 232, (1) RJ11 for RPO
(Remote Power Off)
Slot
(1) slot for Mini-Slot communication card
[Network Management Card (SNMP/Web), NMC
ModBus/JBus, MC Contacts/Serial]
STANDARD AND CERTIFICATION
Performance and Safety
IEC 62040-1/CEI 60950/UL 1778 and CSA 22.2 Standards
EMC
IEC 62040-2; EN 50091-2; FCC class A
WARRANTY
Two years, parts and labor (US and Canada)
- Due to continuing product improvement programs, specifications are subject to change without notice
- Default voltage
- Configurable to daily or monthly
EX RT INDIVIDUAL MODULES AND OPTIONS
Part Number and Description |
5 kVA/4 kW |
7 kVA/4.9 kW |
11 kVA/8 kW |
EX RT Power and Battery Modules |
|
|
|
Power Module with rails |
86215 |
86216 |
86217 |
Battery Module with rails |
86207 |
86207 |
86209 |
UL924 Battery Module |
86218 |
86219 |
86220 |
EX RT Transformer |
|
|
|
7 kVA Transformer with rails |
|
86311 |
|
11 kVA Transformer with rails |
|
|
86211 |
EX RT CLA Charger Module |
|
|
|
CLA Charger with rails |
86214 |
86214 |
86214 |
Battery Integration Kit with Casters |
|
|
|
Stack kit with inter-module fastening, swivel wheels, brakes, leveling feet |
86005 |
86005 |
86005 |
EX RT INDIVIDUAL MODULES AND OPTIONS
Part Number and Description |
5 kVA/4 kW |
7 kVA/4.9 kW |
11 kVA/8 kW |
EX RT Power and Battery Modules |
|
|
|
Power Module with rails |
86215 |
86216 |
86217 |
Battery Module with rails |
86207 |
86207 |
86209 |
UL924 Battery Module |
86218 |
86219 |
86220 |
EX RT Transformer |
|
|
|
7 kVA Transformer with rails |
|
86311 |
|
11 kVA Transformer with rails |
|
|
86211 |
EX RT CLA Charger Module |
|
|
|
CLA Charger with rails |
86214 |
86214 |
86214 |
Battery Integration Kit with Casters |
|
|
|
Stack kit with inter-module fastening, swivel wheels, brakes, leveling feet |
86005 |
86005 |
86005 |
Ordering Information: EX RT MODELS
Catalog
Number |
Style Number |
Form Factor |
Rating (VA/Watts) |
Output Voltage |
Input Connection |
EXRTG5000-XL6UMS |
86505 |
Rack/Tower |
5000/4000 |
HV |
Hardwired |
EXRTG7000-XL6UMS |
86507 |
Rack/Tower |
7000/4900 |
HV |
Hardwired |
EXRTG11000-XL6UMS |
86511 |
Rack/Tower |
11000/8000 |
HV |
Hardwired |
EXRTL5000-XL9UMS |
86506 |
Rack/Tower |
5000/4000 |
LV |
Hardwired |
EXRTL7000-XL9UMS |
86508 |
Rack/Tower |
7000/4900 |
LV |
Hardwired |
EXRTL11000-XL9UMS |
86512 |
Rack/Tower |
11000/8000 |
LV |
Hardwired |