| Specifications
|
Standalone RT
5 kVA (3U)
|
Scalable Frame (16U)
|
|
Rating (kVA) / (kW)
|
5 kVA / 4.5 kW
|
15 kVA / 13.5 kW
|
20 kVA / 18 kW
|
| |
|
Inputs
|
|
| Technology |
on-line double conversion with power factor correction, convection cooled static bypass switch |
| Input connections |
Terminal block with standard NEMA L6-30P, 10’ cord |
Terminal Block |
| Nominal voltage |
200/208 (default) /220/230/240/250 V |
| Voltage range without using battery (1) |
120 - 280 V |
| Input frequency range, THDI |
40-70 Hz, < 7% |
|
Outputs
|
|
| Output connections |
Terminal block + (4) NEMA L6-30R |
Terminal block + (8) NEMA L6-30R |
| Output voltage and frequency, THDU, efficiency (2) |
200/208/230/240 /250 V, 50 / 60 Hz autoselect, frequency converter as standard, <2%, 97% |
|
Transformer – 120V
|
|
| Input connection |
NEMA L6-30P |
| Output connections |
(2) NEMA L5-20R (6) NEMA 5-15/20R |
|
Backup time (3)
|
|
| Pulsar MX standard backup time |
5 minutes |
| Pulsar MX + EXB / MX + 2 EXB / MX + 3 EXB |
22 / 41 / 62 minutes |
22 min (3 EXB)/41 min |
22 min (4 EXB)/41 min (6 EXB)/62 min (9 EXB) (8 EXB)/62 min (12 EXB) |
|
Communications
|
|
| Slots |
(1) minislot compatible with Minislot NMC, |
(2) minislot compatible with Minislot NMC, NMC ModBus/JBus, MC Contacts/Serial NMC ModBus/JBus, MC |
| Ports |
Remote Power off (RJ12), 5 output contacts (DB9), setup using Solution-Pac(4) (USB and DB9-serial ports), EXB module detection (RJ45) |
|
Operating conditions, standards & approvals
|
|
| Performance, safety, EMC, surge protection |
IEC/EN 62 040-3, IEC/EN 62 040-1-1, IEC/EN 62 040-2 class A , UL 1778 and CSA 22.2 |
| Operating temperature, noise, approvals |
0°C to 40°C continuous, 45 dbA (5), UL, cUL, TüV, GS mark, CB, C-Tick, CE, IEC 61 931 |
|
Dimensions/Weight
|
|
| Pulsar MX RT standard backup Tower configuration (WxHxD) |
17.5” x 5.14” x 27.6”/444.5mm x 130.6mm x 700mm |
17.5" x 31.3" x 29.1" / 445mm x 795mm x 738mm |
| Rackmount |
3U x 17.5”/3U x 444.5mm |
17.5" x 27.1" x 29.1" / 445mm x 688mm x 738mm |
| Weight |
125.7 lbs / 57 kg |
428 lbs / 194 kg |
517 lbs / 235 kg |
| Pulsar MX Transformer 5000 (WxHxD) |
17.5” x 3.5” (2U) x 25.6”/444.5mm x 88.9mm x 650mm – 84 lbs/38 kg |
| |
1 per UPS |
up to 3 |
up to 4 |
| MX EXB battery unit tower / rack (WxHxD) |
"17.5” x 5.14” (3U) x 25.6”/444.5mm x 130.6mm x 650mm - 154 lbs/70 kg maximum three per power module |
|
Warranty
|
Two Year |
| |
|
Part numbers
|
Pulsar MX 5000 RT
Pulsar MX UPS - standard backup time |
87050 |
87415 (7) |
87420 (8) |
| Pulsar MX UPS - standard backup time with 120V Transformer (2U) |
87150 |
-- |
-- |
| Pulsar MX EXB RT : battery extension module (3U) |
87103 |
| Pulsar MX 16U Frame - Empty |
-- |
87021 |
| Caster/Floor Mount Kit for Pulsar MX Frame |
-- |
87410 |
| MX FRAME Rail Kit |
-- |
87418 |
| Pulsar MX Transformer 5000 RT with rails (2U) |
87102 |
| Pulsar MX Power / electronics sub-module |
87100 |
| Pulsar MX Battery / sub-module |
87101 |
| Battery Integration System |
86005 |
| Pulsar MX 6-foot battery cable |
68528 |
| MX/EX RT Rail Kit |
86002 |