Bomara Associates Logo Bomara Associates Homepage Eaton Authorized Power Specialist

Powerware Rackmount Specifications

Powerware Rackmount Features
Powerware Rackmount Runtime Matrix

UPS Series: 5115 5125 5140 9125 9170+ | 9170+RM Ferrups
Topology Line Interactive Double-Conversion Online Ferroresonant
Output VA
Rating
500/750/1050/1500 1000/1440/2400/2880 6000

700/1000/1250/1500/2000
2500/3000/5000/6000

3000/6000/9000
12000/15000/18000
850/1150/1400/1800/2100
3100/4300/7000
Output Wattage
Rating
350/520/670/1000 900/1340/2250/2700 6000
1750/2100
490/700/875/1050/1400
1750/2100/3500/4200
2500/5000/7500
10000/12500/15000
600/800/1000/1250
1500/2200/3000/5000
Rack Height 1U 2U 6U 2U 10U-34U 6U-11U
Electrical Input
Nominal Voltage
(VAC)
120 and 230 208, 230 and 240 120 208, 230 and 240 208-240 or 200/100
208/120, 22/110, 240/120

120, 208, or 240 (60Hz)
220, 230, or 240 (50 Hz)

Nominal Voltage
Range (V)
120 V: 96 - 144 120 V: 77 - 152 V
230 V: 154 - 288 V
208/230 V: 160 - 288 V 120 V: 80-144 V
208/230 V: 160 - 288 V
176 - 276 V
208 - 240 V
240 V: 192 - 276 V
Operating
Frequency
50/60Hz, Auto-sensing 50 Hz or 60 Hz
Electrical Output
On Utility Voltage
Regulation
-10% to +6% of nominal
±3% of nominal
On Battery Voltage
Regulation
±5% RMS
±3% of nominal
Voltage Wave
Shape (on battery)
True Sine Wave
Frequency
Regulation
----
----
±3 Hz online; ±0.1 Hz on battery
Load Crest Factor
3 to 1 ratio
Load Segments
(Receptacle Groups)
2
2-3
5
3
----
----
Battery
Internal Battery
Type
Maintenance-free, sealed, valve-regulated lead-aciod (VRLA)
Recharge Time
<3 hours to 90% usable capacity
Battery Dependant
Transfer Time
2-4ms
0ms
N/A
0ms
Communications
Network Transient
Protector
Yes
No
Yes
No
REPO Port
No
Yes
X-Slot Interface
Yes
Non X-Slot Adapter
Yes (2)
Non X-Slot adapter
Standard
Communications
1 x RS-232 Serial Port
& 1 x USB port
1 x RS-232 Serial Port
2 x RS-232 Serial Port
700-3000 VA: 1xRS-232
5000/6000 VA: RS232 & USB
1 x RS-232 Serial Port
General
Dimensions
(HxWxD) Inches
500-1500 VA
1.75x17.3x22.8
1000-1440 VA:
3.5x19.0x19.4
2400-3000 VA:
3.5x19.0x24.5
6000 VA
10.5x17.25x24.3
700-2000 VA:
3.5x19.0x19.4
2500-3000 VA:
3.5x19.0x23.9
5000/6000 VA:
8.63x17.37x24.94

3-Slot: 17.8x17.0x25.4
6-Slot: 31.5x17.0x25.4
9-Slot: 45.0x17.0x25.4
12-Slot: 58.0x17.0x25.4

850-1400 VA:
9.75x16.0x21.25
1800-3100 VA:
9.75x16.0x26.25
4300-7000 VA:
19.0x16.0x26.25
Weight (lb)
35.2/41.4/41.4/48.6
61.0/61.0/89.0/89.0
250
34.0/34.0/50.0/50.0/50.0/
81.5/81.5/206/206
66/103/158/196/
158/196
105/135/150/209/
220/238/495/580
Availible colors
Gray
Gray of Black
Gray
Gray or Black
Gray or Black
Gray
Rail Kit
Included
Optional
Included
Optional
Optional
Included
Environmental
Safety Markings
UL, cUL, C-Tick
CE, TUV
UL, cUL, NOM,
C-Tick, CE
UL, CSA, NOM,
CE, VDE
UL, CSA, NOM, VDE
CE, S, D, N, FI, B, NOM, R
UL, cUL, TUV, CE,
C-Tick, BCIQ

IL, CSA (CUL), CE, TUV

EMC Compliance

FCC Part 15
subpart J Class A
ICES-003; EN 50091-2

FCC Part 15
EN50091-2,
Class A + B

FCC-A, CISPR-A;
VCCI

FCC Class B and VCCI Class II,
3000 FCC Class A
FCC Class A
FCC Part 15:
Class A & B
Internal Fans
for Cooling
Yes
Operating
Temperature
0 to 40ºC (32 to 104ºF)
Relative Humidity
0% to 95% non-condensing
Surge Suppression
ANSI C62.41 Category A (formerly IEEE 587)
Audible Noise
Less than 40 dBA typical
Less than 55 dBA typical
Altitude

Up to 3000M (10,000 ft) without derating

1. Specifications typical and subject to change without notice.

Powerware Rackmount Features
Powerware Rackmount Runtime Matrix



Powerware Home
Bomara Homepage
Request Information

Bomara Associates Phone: 800.5BOMARA (800.526.6272) Phone: 978.452.2299 Fax: 978.452.1169 3 Courthouse Lane, Chelmsford, MA 01824 USA
email: bobr@bomara.com      web: www.bomara.com
Serving the marketplace for over 35 years