BLUEstreak Series
BLUEstreak is Unipower Corporation’s new generation high density hotswappable, modular Front-Ends and Rectifiers producing up to 2000 watts output power. There are 6 standard models with different output voltages and power levels. The modules are ultra-compact with power density up to 24 watts per cubic inch. The modules have automatic load sharing and active output ORing circuit so they can be hot-swapped while the system is
operating.
Using PMBus compliant serial communications, status and control data can be passed between a host system or power management unit and the module.
Front panel mounted LEDs indicate various status or fault conditions and +5V & 12V standby outputs are included.
Operating temperature range is -40°C to +70°C.
FEATURES
- Up to 92% Efficiency
- 1U High: 1.6”
- -40°C to +70°C Operation
- Wide Range AC Input
- Up to 2000W Output
- >0.98 Power Factor
- Output Voltages: 12 to 54.4VDC
- Power Density to 24W/Cu. Inch
- Hot Swappable
- Class B EMI Filter
- LED Indicators
- PMBus Serial Communications
- Variable Speed Cooling Fans
Technical Specidications:
Input |
Voltage Range |
See Model Table |
Power Factor |
>0.98 |
Total Harmonic Distortion, Max |
5% |
Frequency |
47-63Hz |
Inrush Current Limiting, Max |
50A Peak |
EMI Filter, Conducted |
FCC20780 pt 15J Curve B; EN55022 Curve B |
Fast Transients |
EN61000-4-4 |
Surges |
EN61000-4-5 |
Remote Adjust |
0 to +5V |
Input Protection |
Internal Fuse, 25A |
Output |
Current & Voltage |
See Table |
Output Power |
1200-2000W |
Voltage Adjustment Range: |
|
48V / 544V |
30-60V |
24V / 272V |
15-30V |
12V / 136V |
7.5-15V |
Standby Output |
+5V@1.8A; +12V@0.8A |
Line & Load Regulation, Max |
0.30% |
Holdup Time |
10msec |
Overvoltage Protection |
Latch Off |
Filtering: Wideband Noise, 20MHz BW |
200mV |
Current Limit |
105-115% Rated Current (Programmable) |
Effi ciency (54.4VDC @ 2000W rated): |
|
100% Load |
to 91.6% |
75% Load |
to 92.0% |
40% Load |
to 91.0% |
Safety Standards: |
UL60950-1, CSA22.2 No 60950-1, EN60950-1 |
Status Indicators |
Status |
Green LED |
Fault |
Red LED |
Alarm Signals (open drain, TTL compatible) |
ACOK |
AC present, 5V standby operating |
DCOK |
DC output within -10% of nominal |
TEMPOK |
Internal temperature within limits |
FANOK |
Fans running correctly |
PMBus |
Version Compliance |
1.1 |
Environmental |
Operating Temp Range |
-20°C to +70°C |
Output Current Derating |
2.5%/°C, 50°C to 70°C |
Storage Temp Range |
-40°C to + 85°C |
Humidity |
0% to 95%, Non-Condensing |
ESD |
Bellcore GR-1089-Core and EN61000-4-2 |
MTBF, 35oC (Bellcore) |
200,000 Hours |
Cooling |
Integral Ball Bearing Fans |
Physical Specifications |
Case Material |
Steel |
Dimensions, Inches (mm) |
1.60 H x 4.00 W x 13.70 D; (40.6 x 102 x 347.9) |
Weight |
4.0 lbs (1.8 kg) |
SIGNAL PIN CONNECTIONS |
| PIN |
FUNCTION |
PIN |
FUNCTION |
| A1 |
MODULE PRESENT |
C1 |
Sense +Ve 4 |
| A2 |
GA6 |
C2 |
Current Monitor 4 |
| A3 |
GA3 |
C3 |
GA1 |
| A4 |
Standby Return |
C4 |
5V Standby 1, 3 |
| A5 |
FANOK |
C5 |
DCOK |
| A6 |
SMBALERT |
C6 |
SCL |
| B1 |
Sense -Ve |
D1 |
Remote Adjust 4 |
| B2 |
Control |
D2 |
Current Share 4 |
| B3 |
GA2 |
D3 |
GA0 |
| B4 |
Standby Return |
D4 |
12V Standby 2, 3 |
| B5 |
TEMPOK |
D5 |
ACOK |
| B6 |
SDA |
D6 |
ENABLE |
LED indicators:
Green LED (Top)
| LED Status |
Condition |
| ON |
DCOK is TRUE |
| FLASHING |
DCOK is FALSE - unit inhibited |
| OFF |
DCOK is FALSE - unit not inhibited |
Red LED (Bottom)
| LED Status |
Condition |
Possible causes |
| ON |
DC output OFF |
Temperature above/below allowed limits.
OVP.
Overcurrent or Short Circuit (DCOK goes FALSE).
Processor Failure. (Green LED OFF). |
| FLASHING |
DC output ON
(warning) |
Fans below expected speed.
Temperature high/low.
Output current close to maximum.
Output on but DCOK FALSE.
AC input voltage outside range. |
| OFF |
DC output ON |
|
PUSH BUTTONS:
The two push buttons located just above the LEDs can be used to adjust
the
output voltage when the output is enabled. These buttons are labelled
V▲ and
V▼. Short presses for a fraction of a second adjust the output
voltage at the
output voltage setting resolution. If the button is held down, the rate
of change
increases to around 1V/s after 10s. If both buttons are pressed together,
the
button adjust is cleared to zero. The PMBus can read the button adjust
value
and also clear the value. The PMBus can also be used to enable or disable
the buttons.
PMBus SPECIFICATIONS:
PHYSICAL ADDRESSING
The module responds to a single PMBus address. Multiple units can
be used together on a single bus by configuring each module with a
different physical address. Five of the address bits are brought out
on
the module connector and these may be either tied high (to 5VSB) or
low (to SBReturn) to configure the address. The other two bits GA5
and GA4 are internally set to low and high respectively. The table
below summarizes the addressing capability. This gives the module
32 possible addresses, in two banks of 16.
| GA6 |
GA5 |
GA4 |
GA3 |
GA2 |
GA1 |
GA0 |
R/W |
| A2 |
0 |
1 |
A3 |
B3 |
C3 |
D3 |
x |
BUS SPEED
| Minimum |
10kHz |
| Maximum |
100kHz |
DC SPECIFICATIONS
| Vil, SMBus signal input low |
0.8V max. |
| Vih, SMBus signal input high |
2.1V min. / 5.0V max |
| Vol, SMBus signal output low (@pullup) |
0.4V min. |
| Ipullup Current sinking, Vol=0.4V |
4mA min. |
| Ci, capacitance of SCL or SDA pin |
25pF max |
FAULT REPORTING
faults are reported using the SMBALERT signal. This allows the bus
master to determine if a fault has occurred so that it can quickly determine
which module has a fault.
Packet Error Checking (PEC)
The Bluestreak PMBus implementation supports
packet error checking. The user may configure messages with an additional
CRC check byte at the end. Any errors will cause an alert enabling
the master to resend the message. Messages received from the module
also have a PEC byte appended to the end. This byte may be read if
required or only
the message bytes may be read.
PMBus pin summary
The following table is a summary of all available PMBus pins with a
short description of the function of each.
| Pin |
Name |
Function |
| C6 |
SCL |
SMBus Serial Clock |
| B6 |
SDA |
SMBus Serial Data |
| D3 |
GA0 |
Address Configuration |
| C3 |
GA1 |
Address Configuration |
| B3 |
GA2 |
Address Configuration |
| A3 |
GA3 |
Address Configuration |
| A2 |
GA6 |
Address Configuration |
| A6 |
SMB ALERT |
Alert Interrupt Signal |
| B2 |
CONTROL |
Can be configured to turn the unit
ON/OFF |
PMBus Comand Summary:
|