Bomara Associates Logo

Unipower - Presented by Bomara Associates

Bomara Associates Homepage

DPB1U Series

>> Pictures and Diagrams
<< Back to Unipower Telecom Home

KEY FEATURES

  • One Rack Space High (1.75")
  • 19- or 23-Inch Rack Mounting
  • Magnetic Circuit Breakers
  • Single Bus with 1 to 6 Breakers
  • Dual Bus (A/B) with 2 to 12 Breakers
  • Voltage: 12, 24, or 48 VDC
  • Positive or Negative Ground
  • A & B are Isolated Loads
  • A & B Can Be Separately Configured
  • 1A to 50A per Breaker
  • Bus Capacity: 150A per Bus
  • Green/Red LED Breaker Alarm
  • Two Form C Relay Contacts per Bus (A/B)
  • Rack Offset Every ¼" from Front to Back
  • Fail Safe Option

DESCRIPTION

Unipower Telecom's DPB1U Series of circuit breaker panels provide distribution and overload protection for 2 to 12 DC circuits. The panels are only one mounting position (1.75 inches) high. The panel provides 1 to 6 single-bus breakers or 2 to 12 dual-bus (A&B) breakers (1 to 6 per bus). The panels distribute up to a total of 300 amperes of load current from a single or two separate 150-ampere sources with true A and B distribution and alarm capabilities. A and B sections of the dual-bus panel are isolated and can be separately configured for 12, 24, or 48 volts, positive or negative ground. Breaker capacities are from 1 to 50 amperes.

Breaker alarm is indicated by a dual-color LED (green/red) for each bus and two Form C relay contacts per bus.

A fail safe option lets the A and B sides operate redundantly from two separate feeds.

The panels come with brackets that permit mounting in either a 19- or 23-inch relay rack. They can be mounted from the front of the rack with offsets every quarter-inch front to back to align with existing rack-mounted equipment.

 

DC DISTRIBUTION PANELS

MODEL NUMBER BUS BREAKERS
DPB1U-A
DPB1U-A-B
Single 150A
Dual 150A
1-6
1-6 / 1-6

 

TECHNICAL SPECIFICATIONS

INPUT / OUTPUT

  • Panel Capacity: 150A Per Bus, 300A Total
  • Configuration
    • Single Bus with 1 to 6 Breakers
    • Dual Bus with 1 to 6 Breakers Each
  • Breaker Capacity1: 1A to 50A
  • Voltage2
    • 48V Version: 42-60 VDC
    • 24V Version : 21-30 VDC
    • 12V Version: 10.5-15 VDC
  • Polarity2: Positive or Negative Ground

ALARMS

  • Alarm Indicator: Dual-Color LED Per Bus
  • LED Status Indication
    • Green = Normal
    • Red = Alarm
    • Off = No Power
  • Alarm Connections: Two Form C Relay Contacts Per Bus

SAFETY STANDARDS: UL1950, CSA22.2 #950, EN60-950

ENVIRONMENTAL

  • Operating Temp. Range: -10°C to +70°C
  • Storage Temp. Range: -40°C to +85°C
  • Humidity: 0% to 95%, Non-Condensing

PHYSICAL

  • Case Material: Steel
  • Finish: Powder Coat Gray
  • Dimensions3: 1.75"H x 19.00"W x 9.00"D (44.5mm x 483mm x 229mm)
  • Weight: 10.30 lbs (4.67 kg)
  • Rack Mounting Width: 19 or 23 inches

CONNECTIONS

  • Input Connections: Crimp Type Lug or ¼-20 Studs
  • Output Connections
    • 1-30A: Barrier Terminal Strips, #6-32
    • 40-50A: Barrier Terminal Strips, #10-32
  • Chassis Ground Connection: #8-32 Stud
  • Fail Alarm Connections: 0.045" sq. Wirewrap Pins

NOTES:

  1. See table for breaker capacities.
  2. See Ordering Guide to specify voltage and polarity.
  3. For unit with fail safe option the case depth is 10.44 inches (265mm).



Unipower Telecom Home