DPK1U Series
>> Pictures and Diagrams
<< Back to Unipower Telecom Home

KEY FEATURES
- One Mounting Position High (1.75")
- 19- or 23-Inch Rack Mounting
- Type KTK Fuses
- Single Bus with 5 Fuses
- Dual Bus (A/B) with 5 Fuses per Bus
- Bus Capacity: 150A per Bus
- Operating Voltage: 12, 24, or 48 VDC
- Positive or Negative Ground
- A & B are Isolated Loads
- A & B Can Be Separately Configured
- 0.1A to 30A Fuses
- Green/Red LED Fuse Alarm
- Two Form C Relay Contacts per Load
- Green LED Individual Fuse Alarms
- Fail Safe Option
- Rack Offset Every ¼", Front to Back
|
DESCRIPTION
Unipower Telecom's DPK1U Series of Type KTK fuse distribution panels provide distribution and overload protection for 5 or 10 circuits. The one mounting position high (1.75 inches) Type KTK fuse panels provide 5 single-bus fuses or 10 dual-bus (A&B) fuses (5 per bus). They distribute up to a total of 300 amperes of load current from two separate 150-ampere sources with true A and B distribution and alarm capabilities. A and B sections of the dual-bus panel are isolated and can be separately configured for 12, 24, or 48 volts, positive or negative ground. Fuse sizes are 0.1 to 30 amperes.
Fuse alarm is indicated by a dual-color LED (green/red) for each bus and two Form C relay contacts per bus. An individual fuse alarm is indicated by a green LED for each fuse.
The panels come with brackets that permit mounting in either a 19- or 23-inch relay rack. They can be mounted from the front of the rack with offsets every quarter-inch from front to back to align with existing rack-mounted equipment. |
DISTRIBUTION PANELS
| MODEL NUMBER |
BUS |
FUSES |
DPK1U-A
DPK1U-A-B |
Single 150A
Dual 150A
|
5
5 / 5
|
DPK1U-A is a single-ended distribution panel. DPK1U-A-B is a dual-ended distribution panel for distributed power and/or redundancy applications.
TYPE KTK FUSES
| AMPS |
BUSSMAN # |
5 |
KTK-5
|
10 |
KTK-10
|
15 |
KTK-15
|
20 |
KTK-20
|
25 |
KTK-25
|
30 |
KTK-30
|
Order fuses separately. Unipower Telecom recommends Bussman fuses for this panel. They may be ordered from Unipower Telecom or directly from Bussman. Use part number from the table.
Crimp type lugs should be ordered separately. For a kit of 4 two-hole lugs for no. 6 AWG wire, order no. 775-1434-0000, $20.00.
TECHNICAL SPECIFICATIONS
INPUT / OUTPUT
- Panel Capacity: 150A Per Bus, 300A Total
- Configuration
- Single Bus with 5 Fuses
- Dual Bus with 5 Fuses Each
- Fuse Type: Type KTK
- Fuse Capacity1: 0.1A to 30A
- Voltage2
- 48V Version: 42-60 VDC
- 24V Version : 21-30 VDC
- 12V Version: 10.5-15 VDC
- Polarity2: Positive or Negative Ground
ALARMS
- Bus Alarm Indicator: Dual-Color LED Per Bus
- LED Status Indication
- Green = Normal
- Red = Alarm
- Off = No Power
- Bus Alarm Connections: 2 Form C Relay Contacts Per Bus
- Fuse Alarm Indicators: Green LED Per Fuse
SAFETY STANDARDS: UL1950, CSA22.2 #950, EN60-950 |
ENVIRONMENTAL
- Operating Temp. Range: -10°C to +70°C
- Storage Temp. Range: -40°C to +85°C
- Humidity: 0% to 95%, Non-Condensing
PHYSICAL
- Case Material: Steel
- Finish: Powder Coat Gray
- Dimensions: 1.75"H x 19.00"W x 9.00"D (44.5mm x 483mm x 229mm)
- Weight: 9.13 lbs (4.14 kg)
- Rack Mounting Width: 19 or 23 inches
CONNECTIONS
- Input Connections: Crimp Type Lug or ¼-20 Studs
- Output Connections: Barrier Terminal Strips
- Chassis Ground Connection: No. 8-32 Stud
- Fail Alarm Connections: 0.045" sq. Wirewrap Pins
NOTES:
- See table for fuse sizes.
- See Ordering Guide to specify voltage and polarity.
|

NOTE: If section B is not used, a blank panel is installed at the factory. The sum of all fuse currents on either side must not exceed 150 amperes.
|