Gravitas X100
>> Configuration / Ordering Guide
>> Pictures and Diagrams
<< Back to Unipower Telecom Home

KEY FEATURES
- Compact, 2U High
- Fully Integrated System
- Hot-Swap Rectifier Modules
- Remote Access Controller
- Up to 100A at +13.6VDC
- Up to 99A at +27.2VDC
- Up to 75A at -54.4VDC
- Flexible Configuration
- Quick-Connect Terminals
- Universal AC Input
- Power Factor Corrected
- 2+1 Redundant Operation
- 2 Battery Strings
- 2 Battery String Breakers
- Flexible Distribution
- LV Battery Disconnect
- Intelligent Controller
- Ethernet Communication
- SNMP Alarm Option
- Quick, Easy Installation
- 19- or 23-Inch Rack Mounting
|
DESCRIPTION
Gravitas X100 is an ultra-compact, integrated DC power system. It consists of up to three high power-density, hot-swap rectifier modules which can produce up to 75 amperes at -54.4VDC, 99 amperes at +27.2VDC or 100 amperes at +13.6VDC. In 2+1 redundant operation the output current is up to 50 amperes at -54.5VDC, 66 amperes at +27.2VDC or 100 amperes at +13.6VDC.
The system has a configurable DC distribution panel with options for up to 10 load circuits protected either by GMT fuses or circuit breakers. Two battery breakers and a low-voltage battery disconnect are included as standard. The system also has a temperature probe for temperature compensated output from the rectifiers and an optional second probe can be used to monitor external temperature.
The intelligent control and supervisory unit communicates directly with the rectifiers to monitor and control their function. This module features a keypad and a back-lit 2 line alphanumeric display. All system parameters can be controlled by the keypad. Alternatively, the system can be controlled by software from a remote PC via the Ethernet LAN port, using an on-board web server which can be accessed by any standard Java-enabled web browser.
The complete Gravitas X100 is only 2U high (3.47 inches or 88.1mm) and is easily installed by a qualified technician. All connections are at the rear to terminal blocks. A comprehensive operating manual explains all the details of operation and installation. The unit may be mounted in a 19 or 23 inch rack. |
GRAVITAS X100 SYSTEM CAPABILITY
| |
X100-48 |
X100-24 |
X100-12 |
System Voltage
System Max. Current
System Current, 2+1 |
-54.4VDC
75A
50A |
+27.2VDC
99A
66A |
+13.6VDC
100A
50A |
| Max. # of Rectifiers |
3 |
3 |
2 |
Battery String Breakers
Low Voltage Disconnect (battery disconnect) |
2 Standard
Standard |
Max. Total DC Loads
Option A - Miniature Breakers
Option B - GMT Fuses
Option C - Bulk Feed Breakers |
10
1-40A x 2, 1-30A x 6
0.5-12A x 10
1-50A x 4 |
Controller Features
Alarm Outputs
External Digital Inputs
Temperature Compensation |
4
1
Standard (1 probe supplied)
|
Communications
Ethernet TCP/IP
SNMP |
Standard
Optional
|
| Shelf Height |
2U |
| Mounting Width |
19" (23" mounting brackets can be supplied) |
RECTIFIER MODULES
MODULE MODEL # |
OUTPUT VDC |
OUTPUT AMPS |
SYSTEM MODULES |
MAX. SYSTEM AMPS |
N+1 MODULES |
N+1 SYSTEM AMPS |
INPUT VAC |
RPCP48/25-Z
RPCP48/22-Z
RPCM48/15-Z |
-54.4VDC
-54.4VDC
-54.4VDC |
25
22
15 |
3
3
3 |
75
66
45 |
3
3
3 |
50
44
30 |
180-264
90-264
85-264 |
RPCP24/33-Z
RPCM24/25-Z |
+27.2VDC
+27.2VDC |
33
25 |
3
3 |
99
75 |
3
3 |
66
50 |
85-264
85-264 |
RPCP12/50-Z
RPCM12/45-Z |
+13.6VDC
+13.6VDC |
50
45 |
2
2 |
100
90 |
2
2 |
50
45 |
85-264
85-264 |
RECTIFIER MODULE SPECIFICATIONS
INPUT
- Voltage Range
- RPCP48/35: 180-264VAC
- All Other Models: 85-264VAC
- Power Factor: 0.98
- Max. Total Harmonic Distortion: 5%
- Frequency: 47-63 Hz
- Inrush Current Limiting: 50A Peak
- EMI Filter, Conducted: FCC20780 Part 15J Curve B, EN55022 Curve B
- Input Immunity, Conducted
- Fast Transients, Line-Line: ±2kV (EN61000-4-4 Level 3)
- Surges, Line-Line: ±1kV (EN61000-4-5 Level 2)
- Surges, Line-Ground: ±2kV (EN61000-4-5 Level 3)
OUTPUT
- Output Voltage Set, Adjustment Range
- 48V out: 54.4VDC, 45-58VDC
- 24V out: 27.2VDC, 22.5-29VDC
- 12V out: 13.6VDC, 11-14.5VDC
- Output Current: See table above
- Max. Total Regulation: 1.0%
- Holdup Time: 20ms
- Overvoltage Protection
- 48V out : 59V
- 24V out : 29V
- 12V out : 14.5V
|
- Filtering: Wideband Noise, 20MHz BW
- 48V out, P-P: 500mV
- 24V out, P-P: 250mV
- 12V out, P-P: 125mV
- Voice Band Noise: < 32dBmC
- Current Limit: 105% Rated Current
- Efficiency: 82-87%
SAFETY STANDARDS
- UL 1950, CSA22.2-950, EN60950
STATUS INDICATOR
- AC Good: Green LED
- DC Good: Green LED
ENVIRONMENTAL
- Operating Temp. Range: -20°C to +70°C
- Output Current Derating: 2.5%/°C, 50°C to 70°C
- Storage Temp. Range: -40°C to +85°C
- Humidity: 0% to 95%, Non-Condensing
- ESD: Bellcore GR-1089-Core and EN61000-4-2
- Cooling: Internal Fans
|
CONTROLLER FUNCTIONS & FEATURES
PRIMARY FUNCTIONS
- Controls System Rectifiers
- Controls Low Voltage Disconnect
- Monitors System Operating Parameters
- Provides System Alarms
- Provides Remote Access
VISUAL DISPLAYS
- 16 LED Indicators
- 16 Character x 2 Line Alphanumeric
- PC web page via Ethernet TCP/IP
RECTIFIER CONTROL FUNCTIONS
- Battery Float Voltage
- Battery Equalize Voltage
- Battery Voltage Temperature Compensation
RECTIFIER MONITORING DATA
- AC OK (Input)
- DC OK (Output)
- Internal Temperature / Thermal Warning
- Running
- Inventory Data
|
MAJOR SYSTEM PARAMETERS DISPLAYED
- Bus Voltage
- Battery Current
- Rectifier Current
- Load Current
- Battery, External, and Internal Temperatures
ALARM PARAMETERS
- Overvoltage
- Undervoltage
- End Voltage
- Battery Overtemperature
- External Overtemperature
- Internal Overtemperature
- Break/Fuse/Digital Input
- Rectifier Failure
- AC Power Failure
- LVD Failure
ALARM OUTPUTS
- 4 Form-C Relay Contacts
- LED Matrix
- E-mail