Gravitas X150
>> Configuration / Ordering Guide
>> Pictures and Diagrams
<< Back to Unipower Telecom Home

KEY FEATURES
- Compact, 5U High
- Fully Integrated System
- Flexible Configuration
- Hot-Swap Rectifier Modules
- Quick, Easy Installation
- Power Factor Corrected
- AC Line Breakers Option
- Class B EMI Input Filter
- Up to 150A at -48VDC or +24VDC
- Up to 100A in 2+1 Redundant Mode
- Up to 10 DC Circuit Breakers or Fuses
- 2 Battery Strings
- 2 Battery String Breakers
- LV Battery Disconnect
- Intelligent Controller
- Ethernet Communication
- SNMP Alarm Option
- Distribution Section Cover
- Distribution Section Wallet
|
DESCRIPTION
Gravitas X150 is a compact, integrated DC power system. It consists of up to three high power-density, hot-swap rectifier modules which can produce up to 150 amperes at either -48VDC or +24VDC (or up to 100 amperes in 2+1 redundant mode).
The system has a DC distribution panel with up to 10 load circuits which are protected by circuit breakers, GMT fuses, or a combination of the two. Three AC breakers are optional, with one breaker for each rectifier input. Two battery breakers and a low-voltage battery disconnect are included as standard. The system also has a temperature probe for temperature compensated output from the rectifiers and an optional second probe can be used to monitor external temperature.
The intelligent control and supervisory unit communicates directly with the rectifiers to monitor and control their function. This module features a keypad and a back-lit 2 line alphanumeric display. All system parameters can be controlled by the keypad. Alternatively, the system can be controlled by software from a remote PC via the Ethernet LAN port, using an on-board web server which can be accessed by any standard Java-enabled web browser.
The complete Gravitas X150 is only 5U high (8.65 inches or 220mm) and is easily installed by a qualified technician. All connections are at the rear to DIN-rail terminal blocks. A comprehensive operating manual explains all the details of operation and installation. The unit may be mounted in a 19 or 23 inch rack. |
GRAVITAS X150 SYSTEM CAPABILITY
| |
X150-48R/150 |
X150-48R/75 |
X150-24R/150 |
System Voltage
System Max. Current
System Current, 2+1 |
-54.4VDC
150A
100A |
-27.2VDC
75A
50A |
+13.6VDC
150A
100A |
| Input Range, VAC |
170-264 |
85-264 |
85-264 |
Rectifier Model
Max. # of Rectifiers |
RRSI48/50-Z
3 |
RRPI48/25-Z
3 |
RRPI24/50-Z
3 |
| Input Breakers, AC |
3 Optional (one per rectifier module) |
Battery String Breakers
Low Voltage Disconnect (battery disconnect) |
2 Standard
Standard |
Total # of DC Loads
1-50A Breakers
1-20A Breakers
½-12A GMT Fuses |
10
4
6
10 |
Controller Features
Alarm Outputs
External Digital Inputs
Temperature Compensation |
4
1
Standard (1 probe supplied)
|
Communications
Ethernet TCP/IP
SNMP |
Standard
Optional
|
| Rack Height |
5U |
| Mounting Width |
19" (23" mounting brackets can be supplied) |
RECTIFIER MODULE SPECIFICATIONS
INPUT
- Voltage Range
- RRPI models: 85-264VAC
- RRSI models: 180-264VAC
- Power Factor: 0.98
- Max. Total Harmonic Distortion: 5%
- Frequency: 47-63 Hz
- Inrush Current Limiting: 25A Peak
- EMI Filter, Conducted: FCC20780 Part 15J Curve B, EN55022 Curve B
- Input Immunity, Conducted
- Fast Transients, Line-Line: ±2kV (EN61000-4-4 Level 3)
- Surges, Line-Line: ±1kV (EN61000-4-5 Level 2)
- Surges, Line-Ground: ±2kV (EN61000-4-5 Level 3)
OUTPUT
- Output Voltage Set, Adjustment Range
- 48V out: 54.4VDC, 45-58VDC
- 24V out: 27.2VDC, 22.5-29VDC
- Output Current: 100A
- Max. Total Regulation: 1.0%
- Holdup Time: 20ms
- Overvoltage Protection
- 48V out: 59V
- 24V out: 29V
|
- Filtering: Wideband Noise, 20MHz BW
- 48V out, P-P: 500mV
- 24V out, P-P: 250mV
- Voice Band Noise: < 32dBmC
- Current Limit: 105% Rated Current
- Efficiency
- 48V out: 87%
- 24V out: 85%
SAFETY STANDARDS
- UL 1950, CSA22.2-950, EN60950
STATUS INDICATOR
- AC Good: Green LED
- DC Good: Green LED
ENVIRONMENTAL
- Operating Temp. Range: -20°C to +70°C
- Output Current Derating: 2.5%/°C, 50°C to 70°C
- Storage Temp. Range: -40°C to +85°C
- Humidity: 0% to 95%, Non-Condensing
- ESD: Bellcore GR-1089-Core and EN61000-4-2
- Cooling: Internal Fans
|
CONTROLLER FUNCTIONS & FEATURES
PRIMARY FUNCTIONS
- Controls System Rectifiers
- Controls Low Voltage Disconnect
- Monitors System Operating Parameters
- Provides System Alarms
- Provides Remote Access
VISUAL DISPLAYS
- 16 LED Indicators
- 16 Character x 2 Line Alphanumeric
- PC web page via Ethernet TCP/IP
RECTIFIER CONTROL FUNCTIONS
- Battery Float Voltage
- Battery Equalize Voltage
- Battery Voltage Temperature Compensation
RECTIFIER MONITORING DATA
- AC OK (Input)
- DC OK (Output)
- Internal Temperature / Thermal Warning
- Running
- Inventory Data
|
MAJOR SYSTEM PARAMETERS DISPLAYED
- Bus Voltage
- Battery Current
- Rectifier Current
- Load Current
- Battery, External, and Internal Temperatures
ALARM PARAMETERS
- Overvoltage
- Undervoltage
- End Voltage
- Battery Overtemperature
- External Overtemperature
- Internal Overtemperature
- Break/Fuse/Digital Input
- Rectifier Failure
- AC Power Failure
- LVD Failure
ALARM OUTPUTS
- 4 Form-C Relay Contacts
- LED Matrix
- E-mail
- SNMP (Optional)
|
|