Gravitas X410R / X610R-48 Volt DC Hot Swap Power Systems - up to 600A>> Pictures and Diagrams Description:
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Cabinet | Size600mm x 600mm x 2134mm (48RU) |
| Mounting | Floor standing |
| Battery Connection | Front access |
| Load Circuit Breaker Connection | Front access |
| Cable Entry, AC & DC | Top of cabinet |
| Front Doors | Optional |
The X410R system accommodates 2 of the RANGER Series shelves with 4 rectifier modules in each for a total of 8 rectifiers, while the X610R increases this capacity by 50% to 3 shelves and a total of 12 rectifiers. The rectifiers are hot-swap for N+1 redundant operation, providing a high level of system security and ease of maintenance.
| Model | RRSI48/50-Z |
| DC Output Rating | 50A @ 54.4V |
| AC Input Rating | 230VAC – Operating range 170 – 264VAC |
The DC distribution panel includes DIN Rail mounted load circuit breakers for ease of changing in the field or adding as expansion demands. Also included are modular alarm cards for circuit breaker trip alarms, load shunts for sensing rectifier bus and load bus current, and a Low Voltage Disconnect (LVD) contactor to prevent deep discharge of the system battery.
| DC Distribution | |
| Number of breaker positions | 36 X 13mm positions max. for load circuits 2 X 13mm positions for internal aux. circuits |
| Standard ratings | 1A to 60A for single position of 13mm each 80A, 100A require 2 positions of 26mm each |
| Type of CB | DIN Rail mount, Hydraulic-Magnetic, Mid-Trip, Listed UL 489A |
| Alarm Cards | Monitors 12 CB’s each. Max. 3 total required. Cards provide relay alarm contacts to DSC1000 controller |
| Access to CB’s and alarm cards | Removable front panel |
| Load & RectifierBus Shunts | |
| Rating | 50mV at 400A (X410R) or 600A (X610R) each input to DSC1000 Controller/LCD display |
| Low Voltage Disconnect | |
| Disconnect/Reconnect Levels | Programmable through the DSC1000 Controller |
| Contactor Rating | 400A (X410R) or 600A (X610R) |
Each of the 3 battery shelves in the cabinet is protected by a circuit breaker mounted on the front panel. External optional battery racks have individual breaker protection per shelf in its respective rack. Connection to these external racks is made via bus bar connections at the back of the cabinet with back panel removed.
| Rating | 125A |
| Alarm | Alarm contacts from CB to DSC1000 controller |
Input protection to each rectifier is provided via circuit breakers mounted on the front of the AC distribution panel. This panel also has a terminal block input to connect either a single phase or a 3 phase main feed plus ground.
| Number of Breakers | 8 (X410R) or 12 (X610R) |
| Breaker Rating | 25A, 2-pole, UL489 Listed |
| AC input Terminals | L1, L2, L3, N, GND |
The cabinet system incorporates 3 battery shelves, each of which can accommodate a single string of 4 x 12V front connect batteries having a maximum capacity of 170AH using Northstar NSB-170FT, giving a total cabinet capacity of 510AH. Each battery has characteristics defined as follows: (The cabinet is pre-wired with standard battery feed cables from the battery distribution panel and return bus. Additional battery capacity can be provided via optional battery cabinets)
| Model | NSB-170FT |
| Terminals | Front access |
| Voltage | 12V |
| 8 hr capacity to 1.75 volts per cell | 170.8 ampere – hour (AH) |
| Float voltage | 2.27 +/- .02 volts per cell |
| Size | 12.60”/320mm(H) X 4.92”/125mm(W) X 22.05”/560mm(D) |
| Weight | 131.2 pounds (~60Kg) |
The Gravitas DSC1000 is a remote access system controller for telecom power systems. It is used to digitally control and monitor the power system and its components, and to communicate remotely via a network connection. Features and specifications are as follows:
| Rectifier Control Functions (I²C control via RJ11 connector interface to each rectifier shelf) | Battery Float Voltage, Battery Equalize Voltage, Battery Voltage Temp. Compensation, Battery Charge Current |
| LVD (Bat. Low Volt Disconnect) | Programmable disconnect and re-connect voltages for LVD contactor |
| Visual Displays (front panel) | 16 LED indicators for alarm/status, LCD 16x2 matrix display |
| Touchpad Control (front panel) | 8-key, for manual programming and monitoring of system parameters |
| Remote Programming (front Panel) | RS232 interface |
| Relay Alarm Outputs | 8 Form-C relay contacts, 4 pre-defined & 4 user configurable |
| Remote Communication (RJ45) | Ethernet communication, Optional SNMP Built-in WEB server allows access from PC Java enabled WEB browser |
| Remote Comm. of Alarm Parameters (RJ45) | Overvoltage, Undervoltage, End Voltage, Batt. OT, Ext. OT, Fuse/CB Trip, Rectifier Fail, AC Fail, LVD Fail, User Defined (up to 6) |
| AC Input | |
| Input Phase | 1-phase or 3-phase |
| Voltage Range | 170-264VAC phase to phase or phase to neutral |
| Frequency Range | 47-63 Hz |
| Power Factor | Greater than 0.98 |
| Input Protection | 25A, 2-pole breaker, each rectifier |
| Rated Current | 100A input each 3-phase line |
| DC Input | |
| Nominal Voltage | -48V |
| Float Voltage Set-point | -54.4V |
| Voltage Adjustment Range | -46 to -57V (controlled by DSC1000) |
| Maximum System Current | X410R - 400A, (8 rectifiers max. in two 2U shelves)X610R - 600A, (12 rectifiers max. in three 2U shelves) |
| Rectifier Rated Current | 50A |
| Load Bus & Rectifier Bus Metering | X410R - 50mV, 400A shunt for eachX610R - 50mV, 600A shunt for each |
| Environment | |
| Ambient Temperature | 0 to 70°C, derating 2.5%/°C from 50-70°C (not including batteries) |
| Humidity | Less than 95% Non-condensing |
| Cooling | Fan cooling in each rectifier and optional Inverters & DC/DC Converters |