Bomara Associates Logo

Unipower - Presented by Bomara Associates

Bomara Associates Homepage

INV2500-HS Series

>> Pictures and Diagrams
<< Back to Unipower Telecom Home

KEY FEATURES

  • Hot-Swap Replacement in Shelf
  • Two Rack Spaces High (3.5")
  • 19- or 23-Inch Rack Mounting
  • 2500VA Module Output
  • 5000VA for Two Units in 19" Shelf
  • 7.2VA per Cubic Inch Density
  • 115VAC at 22A or 230VAC at 11A
  • Low Distortion 50 or 60Hz Sine Wave
  • 42 to 56 VDC Input
  • Fully Isolated from Battery Input
  • 90% Typical Efficiency
  • Up to 300% Surge Capability
  • Circuit Breaker Input & Output Protection
  • Powers Reactive Loads
  • Form C Relay Alarm Contacts

DESCRIPTION

Unipower Telecom's INV2500-HS Series are 2500 volt-ampere, sine wave, hot-swap inverter modules which are available with a compatible, two-unit 19-inch shelf. The shelf is 2U high (3.5 inches). The units operate off a 48VDC (42-56V range) input and produce either 115VAC output at 22A RMS or 230VAC at 11A RMS. Two units in the shelf produce 115VAC at 44A or 230VAC at 22A. The low distortion 50 or 60Hz sine wave is produced using MOSFET and IGBT power semiconductors with advanced, high-frequency, pulse-width modulation techniques which achieve 90% efficiency and 7.2VA per cubic inch power density.

The units can be paralleled for higher output power for for N+1 redundant applications. When operated in the shelf they are automatically paralleled. They are fully isolated from the telecom battery.

An input circuit breaker turns the inverter on and protects the battery from input faults. An output breaker connects the inverter to the load bus (after synchronization if the bus is live) and quickly disconnects the inverter in the event of an internal fault. The inverter has high surge capability (up to 300%) for starting loads such as motors, but the output breaker quickly trips if power attempts to flow back into a faulted inverter.

Front panel LEDs indicate inverter status, and Form C relay alarm contacts are available on the back. The units are self-cooled by internal fans.

 

SINE WAVE INVERTER MODULES

MODEL INPUT OUTPUT FREQUENCY
INV2500-HS-60-E
INV2500-HS-50-E
42-56VDC
42-56VDC
115VAC @ 22A
115VAC @ 22A
60Hz
50Hz
INV2500H-HS-60-E
INV2500H-HS-50-E
42-56VDC
42-56VDC
230VAC @ 11A
230VAC @ 11A
60Hz
50Hz
INV2500-HS-60*
INV2500-HS-50*
42-56VDC
42-56VDC
115VAC @ 22A
115VAC @ 22A
60Hz
50Hz

* Note: These two models have the AC neutral output grounded to chassis. The other four models (-E) have floating AC neutral outputs.

INVERTER SHELVES

MODEL OUTPUT VOLTAGE SIZE HEIGHT MODULE CAPACITY MAX. OUTPUT
INVR2U-HS
115VAC
19-Inch
2U
2
5kVA
INVR2U-HS-H
230VAC
19-Inch
2U
2
5kVA

Note: The hot-swap shelf comes with a rear, clear plastic safety cover which adds 1.62 inches to its depth. The AC neutral output is floating. 23-inch rack mounting requires panel extenders.

 

TECHNICAL SPECIFICATIONS

Typical at nominal 48VDC input, full load and 25°C unless otherwise noted.

INPUT

  • Voltage Range: 42-56 VDC
  • Input Current, Full Load, 48VDC: <60A DC
  • Input Current, No Load, 48VDC: <1A DC
  • Input Protection: 100A Circuit Breaker
  • EMI Filter, Conducted: FCC2078 Part 15J Curve A, EN55022 Curve A
  • Voice Band Noise, 240 A-H Battery: <32dBmC

OUTPUT

  • Voltage, Full Load: 115 or 230 VAC
  • Voltage, No Load: 120 or 240 VAC
  • Max. Current, 115VAC: 22A RMS
  • Max. Current, 230VAC: 11A RMS
  • Frequency: 50 or 60Hz, ±0.1%
  • Total Harmonic Distortion: <2%
  • Load Crest Factor: 2.8 to 1
  • Output Protection: 25A Circuit Breaker
  • Surge Capability: Up to 300%
  • Reactive Loads: +90° to -90° Phase
  • Efficiency: 90%

SAFETY STANDARDS: UL60950, CSA22.2 #60950, EN60950

STATUS INDICATORS

  • Input OK: Green LED
  • Sync OK: Green LED
  • Output OK: Green LED
  • Form C Relay Alarm Contacts: Inverter Fail Alarm

ENVIRONMENTAL

  • Operating Temperature: 0°C to +70°C
  • Output Current Derating: 2.5%/°C, 50°C to 70°C
  • Storage Temperature: -40°C to +85°C
  • Humidity: 0% to 95%, Non-Condensing
  • Cooling: Internal Fans

PHYSICAL

  • Module Case Material: Aluminum
  • Shelf Material: Steel
  • Dimensions
    • Module: 3.32"H x 8.50"W x 12.25"D (84.3mm x 216mm x 311mm)
    • Rack/Shelf: 3.46"H x 18.32"W x 16.38"D (87.9mm x 465mm x 416mm)
  • Rack Mounting Width: 19 or 23 inches
  • Module Weight: 11.65 lbs (5.3 kg)

 

OUTPUT FOR TWO INVERTERS IN A SHELF

OUTPUT VOLTS OUTPUT kVA OUTPUT AC AMPS
115VAC
5.0
44
230VAC
5.0
22


Unipower Telecom Home
Bomara Homepage
Request Information

Bomara Associates Phone: 800.5BOMARA (800.526.6272) Phone: 978.452.2299 Fax: 978.452.1169 3 Courthouse Lane, Chelmsford, MA 01824 USA
email: bobr@bomara.com      web: www.bomara.com