INPUT / OUTPUT
- LVD Capacity: 400A or 600A Per Load
- Configuration: Single or Dual LVD
- Voltage1
- 48V Version: 42-59 VDC
- 24V Version: 21-29 VDC
- Polarity: Positive or Negative Ground
- LVD Connection: In Series with Battery or Load
- LVD Disconnect Voltage2
- 48V Version: 42.5VDC
- 24V Version: 21.25VDC
- LVD Reconnect Voltage2
- 48V Version: 49.0VDC
- 24V Version: 24.5VDC
ALARMS
- Alarm Connections: Form C Relay Contacts
ENVIRONMENTAL
- Operating Temp. Range: -10°C to +50°C
- Storage Temp. Range: -40°C to +85°C
- Humidity: 0% to 95%, Non-Condensing
|
SAFETY STANDARDS: UL1950, CSA22.2 #950, EN60-950
PHYSICAL
- Case Material: Steel
- Finish: Powder Coat Gray
- Dimensions
- 3.5"H x 19.00"W x 9.00"D (88.9mm x 483mm x 229mm)
- 3.5"H x 23.00"W x 9.00"D (88.9mm x 584mm x 229mm)
- Weight, Dual LVD: 18 lbs (8.2 kg)
- Rack Mounting Width: 19 or 23 inches
CONNECTIONS
- Input & Output: 5/16-18 Bolts
- Chassis Ground Connection: 10-32 Bolt
- Alarm Connections: Miniature Screw Terminals
NOTES:
- See Ordering Guide to specify voltage and polarity.
- Factory setting. These voltages are field adjustable.
|