KEY FEATURES

  • 2U High (3.5")
  • 85-264 or 170-264 VAC Input Range
  • Low Energy Cost: 0.99 Power Factor
  • Active Load Sharing
  • Output Voltage Range: 45-58 or 22.5-29 VDC
  • Group or Individual Remote Output Adjustment*
  • Battery Temp. Compensated Charge Regulation*
  • 85% Efficiency
  • High Power Density: Up to 6.4W per cubic inch
  • Hot-Swappable
  • Integral ORing Diodes
  • Class B EMI Filter

* With external controller

DESCRIPTION

Unipower Telecom's Meridian Series are hot-swappable, modular rectifiers which produce 12.5 or 25 amperes at 54.4VDC (48V version) or 50 amperes at 27.2VDC (24V version). These switching rectifier modules are compact with up to 6.4 watts per cubic inch power density, taking up only 3.5 inches (two mounting positions) of rack space. They are ideally suited for both wireless and wireline applications.

Three rectifier modules in a companion 19-inch shelf produce up to 75A at 54.4VDC or 150A at 27.2VDC. The rectifier modules have automatic load sharing and ORing diodes, so they can be added or replaced while the system is operating. The output voltage of each rectifier module can be adjusted over 45-58 or 22.5-29 VDC from a pot on the front panel, or all modules can be adjusted simultaneously from a remote analog input.

 

RECTIFIER MODULES

MODEL NUMBER NOMINAL OUTPUT FACTORY SET OUTPUT MAX. OUTPUT CURRENT INPUT VOLTAGE RANGE
RMH48/12.5
RMP48/25
RMP24/50
48VDC
48VDC
24VDC
54.4V
54.4V
27.2V
12.5A
25A
50A
85-264VAC
170-264VAC
170-264VAC

SHELVES

MODEL NUMBER WIDTH HEIGHT # OF MODULES
RRS2U-19
RRS2U-23
19" (483mm)
23" (584mm)
3.5" (89mm)
3.5" (89mm)
3
4

TECHNICAL SPECIFICATIONS

Typical at nominal line, full load and 25°C unless otherwise noted.

INPUT

  • Voltage Range
    • RMH: 85-264VAC
    • RMP: 170-264VAC
  • Power Factor: 0.99
  • Max. Total Harmonic Distortion: 5%
  • Frequency: 47-63Hz
  • Inrush Current Limiting: 50A Peak
  • Input Current, Full Load
    • RMH: 6.7A @ 120VAC
    • RMP: 7.0A @ 230VAC
  • EMI Filter, Conducted: FCC20780 Part 15J Curve B, EN55022 Curve B
  • Fast Transients: EN61000-4-4
  • Surges: EN61000-4-5
  • Analog Voltage Adjust: 0 to +5V

OUTPUT

  • Current & Voltage1:
    • 12.5 or 25A @ 54.4VDC
    • 50A @ 27.2VDC
  • Voltage Adjustment Range
    • 48V Nominal: 45-58VDC
    • 24V Nominal: 22.5-29VDC
  • Max. Total Regulation: 1.0%
  • Holdup Time: 20ms
  • Filtering: Wideband Noise, 20MHz BW
    • 48V Out, P-P: 500mV
    • 24V Out, P-P: 250mV
  • Voice Band Noise: < 32dBmC
  • Current Limit: 105% Rated Current
  • Efficiency: 85%
  • Safety Standards: UL1950, CSA22.2-950, EN60950

STATUS INDICATORS

  • AC Good: Logic LO Output
  • DC Good: Logic LO Output

ENVIRONMENTAL

  • Operating Temperature: 0°C to 70°C
  • Derating: 2.5%/°C, 50°C to 70°C
  • Storage Temperature: -40°C to 85°C
  • Humidity: 0% to 95%, Non-Condensing
  • ESD: Bellcore GR-1089-Core and EN61000-4-2
  • Cooling: Internal Fans

PHYSICAL

  • Rectifier Case Material: Aluminum
  • Shelf Finish: Powder Coat Gray
  • Dimensions
    • Rectifier Module: 3.3" H x 4.9" W x 13.1" D (84mm x 124mm x 333mm)
    • 19" Shelf: 3.50" H x 19.00" W x 19.88" D (89mm x 483mm x 505mm)
    • 23" Shelf: 3.50" H x 23.00" W x 19.88" D (89mm x 584mm x 505mm)
  • Weight, Rectifier Module: 9.55 lbs (4.33kg)

NOTES:

  1. Voltage set at factory.