Sigma Series-WM
>> Pictures and Diagrams
<< Back to Unipower Telecom Home

KEY FEATURES
- 48, 24, and 12V Versions
- Low Fan Noise
- Class B Conducted EMI
- DC Good LED
- Universal 85-264VAC Input
- Active Power Factor Correction
- ORing Diode on Output*
- Active Current Sharing*
- Control & Monitoring Features
|
DESCRIPTION
Unipower Telecom's Sigma Series Wall-Mount rectifiers are designed as a quick and easy solution in providing DC power to a variety of telecom equipment.
The 6 available models range in output power from 450W to 650W. Output voltages of 12V, 24V, and 48V are available for applications without batteries. For battery-supported applications, output voltages are pre-set to 13.6V, 27.2V, or 54.4V.
Green LEDs indicate AC and DC power good. The rectifiers also have control and monitoring features and a +5V standby output. Operating temperature range is -20°C to +70°C.
* Where higher power levels than can be obtained from a single unit are required, it is possible to connect two units in parallel. Alternatively, two units connected in parallel where the total load is less than that available from a single unit will provide N+1 redundant operation. |
STANDARD MODELS
| MODEL NUMBER |
MAX. POWER |
OUTPUT VOLTAGE |
OUTPUT CURRENT |
INPUT VOLTAGE |
RSG12/33-WM
RSG24/18-WM
RSG48/10-WM
RSJ48/12-WM |
450W
500W
550W
650W |
13.6VDC
27.2VDC
54.4VDC
54.4VDC |
33.0A
18.4A
10.1A
11.9A |
85-264VAC
85-264VAC
85-264VAC
85-264VAC |
TSG3000-WM
TSG5000-WM
TSG7000-WM
TSJ7000-WM |
450W
500W
550W
650W |
12VDC
24VDC
48VDC
48VDC |
37.5A
20.8A
11.5A
13.5A |
85-264VAC
85-264VAC
85-264VAC
85-264VAC |
Note: The table does not show the independent 5V, 100mA standby output which is standard on all models.
AC LINE CORDS
- 364-1412-0000: 125VAC with NEMA 5-15 plug
- 364-1414-0000: 205VAC with NEMA 6-15 plug
- 364-1421-0000: 85-264VAC, Unterminated
Note: All line cords are 6ft (approx. 1.8m) long, terminated one end with an IEC60320 C-13 connector.
TECHNICAL SPECIFICATIONS
Typical at nominal 115/230VAC line, full load and 25°C unless otherwise noted.
OUTPUT
- Max. Total Continuous Output Power: 450-650 Watts
- Min. Voltage Adjustment Range: ±5%
- Total Regulation1: 2.0%
- Total Regulation, Standby Supply: 5.0%
- Ripple & Noise, Pk-Pk2: 1%
- Holdup Time: 10ms
- Dynamic Response3: 300μs
- Temperature Coefficient: ±0.02%/°C
- Minimum Load: 0A
- Overload Protection: Auto Recovery
- Overvoltage Protection: Latched Shutdown
- Remote Sense: Up to 0.25V Per Wire
- Current Share: ±10% Full Load Rating
- Standby Output: +5V, 100mA
- DC Power Good Signal: Logic Low
- AC Power Fail Signal: Logic High
- Inhibit: Logic Low
- Overtemperature Warning: Logic High
INPUT
- Input Voltage Range: 85-264VAC
- Power Factor: 0.99
- Input Frequency: 47-63Hz
- Inrush Current Limiting: 30A Peak
- Harmonic Distortion: EN61000-3-2
- Input Protection: Internal Fuse, 10A
|
GENERAL
- Efficiency4: 85-90% at Full Load
- Switching Frequency
- PFC Converter: 48-110KHz
- Output Converter: 275KHz Nominal
- Conducted EMI: EN55022 Curve B, FCC20780 Part 15J Curve B
- Min. Isolation, Class I5
- Input-Output: 3000VAC
- Input-Ground: 1500VAC
- Output-Ground: 50VDC
- Input Immunity, Conducted
- Fast Transients, Line-Line: ±2kV (EN61000-4-4 Level 3)
- Surges, Line-Line: ±2kV (EN61000-4-5 Level 3)
- Surges, Line-Ground: ±4kV (EN61000-4-5 Level 4)
- MTBF (Bellcore): 200,000 Hours
- Safety Standards: EN60950, UL60950, CSA22.2-60950
ENVIRONMENTAL
- Operating Temperature: -20°C to 70°C Ambient
- Derating: 2.5%/°C, 50°C to 70°C
- Storage Temperature: -40°C to 85°C
- Cooling: Integral Ball Bearing Fan
PHYSICAL
- Case Material: Aluminum
- Dimensions: 1.6" H x 4.6" W x 14.0" D (40.6mm x 117.0mm x 355.6mm)
- Weight: 2.65 lbs (1.2 kg)
NOTES:
- No load to full load, including line regulation and load regulation.
- 20MHz bandwidth. Measure with 0.1μF ceramic and 10μF tantalum capacitors in parallel across the output.
- <4% deviation recovering to within 1% for 25% load change.
- Typical efficiency is at low end of range for 12V output and at high end of range for 48V output.
- Intput-output isolation figure is for isolation components only. 100% production hipot tested.
|
|