Bomara Associates Logo

Unipower - Presented by Bomara Associates

Bomara Associates Homepage

Sigma Series-WM

>> Pictures and Diagrams
<< Back to Unipower Telecom Home

KEY FEATURES

  • 48, 24, and 12V Versions
  • Low Fan Noise
  • Class B Conducted EMI
  • DC Good LED
  • Universal 85-264VAC Input
  • Active Power Factor Correction
  • ORing Diode on Output*
  • Active Current Sharing*
  • Control & Monitoring Features

DESCRIPTION

Unipower Telecom's Sigma Series Wall-Mount rectifiers are designed as a quick and easy solution in providing DC power to a variety of telecom equipment.

The 6 available models range in output power from 450W to 650W. Output voltages of 12V, 24V, and 48V are available for applications without batteries. For battery-supported applications, output voltages are pre-set to 13.6V, 27.2V, or 54.4V.

Green LEDs indicate AC and DC power good. The rectifiers also have control and monitoring features and a +5V standby output. Operating temperature range is -20°C to +70°C.

 

* Where higher power levels than can be obtained from a single unit are required, it is possible to connect two units in parallel. Alternatively, two units connected in parallel where the total load is less than that available from a single unit will provide N+1 redundant operation.

 

STANDARD MODELS

MODEL NUMBER MAX. POWER OUTPUT VOLTAGE OUTPUT CURRENT INPUT VOLTAGE
RSG12/33-WM
RSG24/18-WM
RSG48/10-WM
RSJ48/12-WM
450W
500W
550W
650W
13.6VDC
27.2VDC
54.4VDC
54.4VDC
33.0A
18.4A
10.1A
11.9A
85-264VAC
85-264VAC
85-264VAC
85-264VAC
TSG3000-WM
TSG5000-WM
TSG7000-WM
TSJ7000-WM
450W
500W
550W
650W
12VDC
24VDC
48VDC
48VDC
37.5A
20.8A
11.5A
13.5A
85-264VAC
85-264VAC
85-264VAC
85-264VAC

Note: The table does not show the independent 5V, 100mA standby output which is standard on all models.

 

AC LINE CORDS

  • 364-1412-0000: 125VAC with NEMA 5-15 plug
  • 364-1414-0000: 205VAC with NEMA 6-15 plug
  • 364-1421-0000: 85-264VAC, Unterminated

Note: All line cords are 6ft (approx. 1.8m) long, terminated one end with an IEC60320 C-13 connector.

 

TECHNICAL SPECIFICATIONS

Typical at nominal 115/230VAC line, full load and 25°C unless otherwise noted.

OUTPUT

  • Max. Total Continuous Output Power: 450-650 Watts
  • Min. Voltage Adjustment Range: ±5%
  • Total Regulation1: 2.0%
  • Total Regulation, Standby Supply: 5.0%
  • Ripple & Noise, Pk-Pk2: 1%
  • Holdup Time: 10ms
  • Dynamic Response3: 300μs
  • Temperature Coefficient: ±0.02%/°C
  • Minimum Load: 0A
  • Overload Protection: Auto Recovery
  • Overvoltage Protection: Latched Shutdown
  • Remote Sense: Up to 0.25V Per Wire
  • Current Share: ±10% Full Load Rating
  • Standby Output: +5V, 100mA
  • DC Power Good Signal: Logic Low
  • AC Power Fail Signal: Logic High
  • Inhibit: Logic Low
  • Overtemperature Warning: Logic High

INPUT

  • Input Voltage Range: 85-264VAC
  • Power Factor: 0.99
  • Input Frequency: 47-63Hz
  • Inrush Current Limiting: 30A Peak
  • Harmonic Distortion: EN61000-3-2
  • Input Protection: Internal Fuse, 10A

GENERAL

  • Efficiency4: 85-90% at Full Load
  • Switching Frequency
    • PFC Converter: 48-110KHz
    • Output Converter: 275KHz Nominal
  • Conducted EMI: EN55022 Curve B, FCC20780 Part 15J Curve B
  • Min. Isolation, Class I5
    • Input-Output: 3000VAC
    • Input-Ground: 1500VAC
    • Output-Ground: 50VDC
  • Input Immunity, Conducted
    • Fast Transients, Line-Line: ±2kV (EN61000-4-4 Level 3)
    • Surges, Line-Line: ±2kV (EN61000-4-5 Level 3)
    • Surges, Line-Ground: ±4kV (EN61000-4-5 Level 4)
  • MTBF (Bellcore): 200,000 Hours
  • Safety Standards: EN60950, UL60950, CSA22.2-60950

ENVIRONMENTAL

  • Operating Temperature: -20°C to 70°C Ambient
  • Derating: 2.5%/°C, 50°C to 70°C
  • Storage Temperature: -40°C to 85°C
  • Cooling: Integral Ball Bearing Fan

PHYSICAL

  • Case Material: Aluminum
  • Dimensions: 1.6" H x 4.6" W x 14.0" D (40.6mm x 117.0mm x 355.6mm)
  • Weight: 2.65 lbs (1.2 kg)

NOTES:

  1. No load to full load, including line regulation and load regulation.
  2. 20MHz bandwidth. Measure with 0.1μF ceramic and 10μF tantalum capacitors in parallel across the output.
  3. <4% deviation recovering to within 1% for 25% load change.
  4. Typical efficiency is at low end of range for 12V output and at high end of range for 48V output.
  5. Intput-output isolation figure is for isolation components only. 100% production hipot tested.


Unipower Telecom Home
Bomara Homepage
Request Information

Bomara Associates Phone: 800.5BOMARA (800.526.6272) Phone: 978.452.2299 Fax: 978.452.1169 3 Courthouse Lane, Chelmsford, MA 01824 USA
email: bobr@bomara.com      web: www.bomara.com
Serving the marketplace for over 35 years