Bomara Associates Logo

Unipower - Presented by Bomara Associates

Bomara Associates Homepage

TWRI6000 Series

>> Pictures and Diagrams
<< Back to Unipower Telecom Home

KEY FEATURES

  • 85% Efficiency
  • Power Factor Correction to EN61000-3-2
  • 10.6W/in3 Power Density
  • Hot-Swap, N+1 Redundant Operation
  • 2U 19-inch or 23-inch Rack Mounting
  • 26.5V-33.5V Output Adjustment Range
  • 28 to 32 VDC Rated Output
  • 2250W Module Output Power
  • Up to 9000W Total Power, Non-Redundant
  • Up to 6750W Total Power, 3+1 Redundant
  • Integral Isolation Diode
  • Output Current Limiting
  • Inrush Current Limiting
  • Remote Output Adjustment

 

 

STANDARD, PRE-SET MODULES

MODEL NUMBER MAX. WATTS RATED OUTPUT VOLTAGE & CURRENT* ADJUSTMENT RANGE INPUT VOLTAGE RANGE MINIMUM LOAD LINE/LOAD REGULATION
TWRI6000
TWRI6001
TWRI6002
TWRI6003
TWRI6004
2250
2250
2250
2250
2250
28V / 80.4A
29V / 77.6A
30V / 75.0A
31V / 72.6A
32V / 70.3A
26.5-33.5VDC
26.5-33.5VDC
26.5-33.5VDC
26.5-33.5VDC
26.5-33.5VDC
170-264 VAC
170-264 VAC
170-264 VAC
170-264 VAC
170-264 VAC
0A
0A
0A
0A
0A
1%
1%
1%
1%
1%

MATING-CONNECTOR KIT: Order number 775-1441-0000

SYSTEM RACKS: Order RRS2U-19 for 3 modules or RRS2U-23 for 4 modules.

* These are the standard, factory-set output voltages. Other voltages can be set.

 

TECHNICAL SPECIFICATIONS

Typical at nominal 230VAC line, full load and 25°C unless otherwise noted.

OUTPUT

  • Max. Total Continuous Output Power: 2250 Watts
  • Voltage Adjustment Range: 26.5-33.5 VDC
  • Total Regulation1: 1.0%
  • Ripple & Noise, Pk-Pk2: 250mV
  • Holdup Time3: 20ms
  • Dynamic Response4: 1ms
  • Temperature Coefficient: 0.05%/°C
  • Minimum Load: 0A
  • Overload Protection: Constant Current Limiting
  • Overvoltage Protection: Latched Shutdown
  • Active Current Share5: 10% Differential from Rated Current
  • Remote Sense: Up to 0.5V Per Wire

INPUT

  • Input Voltage Range: 170-264VAC
  • Power Factor: 0.98
  • Input Frequency: 47-63Hz
  • Inrush Current Limiting: 25A Peak
  • Input Current, Full Load: 11.8A @ 230VAC
  • Input EMI Filter, Conducted: EN55022 Curve B, FCC20780 Part 15J Curve B
  • Harmonic Distortion: EN61000-3-2
  • Input Immunity, Conducted
    • Fast Transients, Line-Line: ±2kV (EN61000-4-4 Level 3)
    • Surges, Line-Line: ±1kV (EN61000-4-5 Level 2)
    • Surges, Line-Ground: ±2kV (EN61000-4-5 Level 3)
  • Input Protection: Internal Fuse, 20A

GENERAL

  • Efficiency: 85% at Full Load
  • Switching Frequency: 70kHz Nominal
  • Overtemperature Protection: Power Shutdown
  • Min. Isolation, Class I6
    • Input-Output: 3000VAC
    • Input-Ground: 1500VAC
    • Output-Ground: 50VDC
  • Safety Standards: EN60950, UL60950, CSA22.2 #60950

ENVIRONMENTAL

  • Operating Temperature: 0°C to 70°C Ambient
  • Derating: 2.5%/°C, 50°C to 70°C
  • Storage Temperature: -40°C to 85°C
  • Cooling: Integral Ball Bearing Fan

PHYSICAL

  • Module Case Material: Aluminum
  • Rack Mount Material: Steel
  • Rack Mount Finish: Powder Coat Gray
  • Dimensions
    • Module: 3.3"H x 4.9"W x 13.1"D (84mm x 124mm x 333mm)
    • 19" Rack: 3.50"H x 19.00"W x 19.88"D (89mm x 483mm x 505mm)
    • 23" Rack: 3.50"H x 23.00"W x 19.88"D (89mm x 584mm x 505mm)

NOTES:

  1. At remote sense point over full line range and 0-100% load change.
  2. 20MHz bandwidth. Measure with 0.1μF ceramic and 10μF tantalum capacitors in parallel across the output.
  3. Full output power at nominal AC line.
  4. <5% deviation recovering to within 1% for 50% load change.
  5. Using single wire current share with remote sense connected.
  6. Intput-output isolation figure is for isolation components only. 100% production hipot tested.


Unipower Telecom Home
Bomara Homepage
Request Information

Bomara Associates Phone: 800.5BOMARA (800.526.6272) Phone: 978.452.2299 Fax: 978.452.1169 3 Courthouse Lane, Chelmsford, MA 01824 USA
email: bobr@bomara.com      web: www.bomara.com