Servertech Home » -48 VDC Power Management » 48DCWC-16-2X100-A0

48DCWC-16-2X100-A0

Product Description Product Image
The Server Technology® -48VDC Switched PDU provides control of outlet power and per-outlet current measurement through the build-in Web andCLI interfaces as well as through SNMP. Temperature and humidity measurements can be provided via optional probes. The Switched “Master” PDUcan be connected to a Switched “Link” PDU to extend the network access to the redundant or secondary power feed.


  • Tech Specs

Technical Specifications for the 48DCWC-16-2X100-A0:


Inputs
Input Voltage(V) -48
Input Terminal (2) x 1/4-20 dual-studs on 5/8 in. centers (100A max)
Input Current(A) 200
Input Current Rated(A) 200
Input Power Capacity (kW) 9.6
Outputs
Terminals (16) x Screw-down terminals (10A max)
Branch Circuit Protection
GMT Fuses Included
Physical
Dimensions 3.5in tall x 17.0in wide x 12.0in deep [89mm x 432mm x 305mm]
Environmental
Operating Environment 32°F to 122°F / 0°C to 50°C | 8%RH to 90%RH non-condensing | 6,500ft/2km elevation
Storage Environment: -40°F to 185°F / -40°C to 85°C | 8%RH to 90%RH non-condensing | 50,000ft/15km elevation
Communications & Security
Communications & Security
  • 10/100 Mbps Ethernet (RJ-45 connector), RS-232 serial (RJ-45 connector)
  • Two (2) temperature/humidity sensor inputs (4P4C), Link port (RJ-12) - {also on Link PDU}
  • Web-browser GUI and command-line interface (CLI): HTTP/HTTPS, TLSv1.2, SSHv2, Telnet, SNMPv2c and v3 (GET, SET, Traps), IPv4 and IPv6, LDAPv3/LDAPS, TACACS+, RADIUS, FTP/SFTP
Certifications
North American
  • cTUVus Mark to UL 60950-1:2007 R10.14
  • CAN/CSA-C22.2 No. 60950-1-07+A1:2011+A2:2014
  • FCC Part 15 Subpart B Sections 15.107 and 15.109, Class A
Global
  • TUV T-Mark to EN 60950-1:2006+A11+A1+A12+A2
  • EMC to EN55024 (2010) and EN55032 (2012)
  • CE Compliant
  • RoHS, European Hazardous Materials Directive (Recast) 2011/65/EU
  • WEEE Compliant
  • NEBS Level 3
  • GR-1089-Core: Sections 1-4, 7, 9, and 10
  • GR-63-Core: Sections 4.1, 4.2, 4.3, 4.4, 4.5, and 4.7
Measurement Accuracy
Input Measurement Accuracy:
  • LED Current = ± 10% at 0.1 amp (0.5 - 9.9 amps) and 1 amp (> 9.9 amps) resolution
  • GUI Current = ± 5% at 0.01 amp resolution (above 0.5 amp)
Optional Accessories
EMTH-2-10 Combination Temperature/Humidity Probe, 10ft (3m)
EMCU-1-1C Environmental Monitor adding:
  • Two (2) EMTH-2-10 temperature/humidity ports (one probe included)
  • One (1) EMWS-1-1 water sensor port (probe sold separately)
  • Four (4) dry contact (NO/NC) monitoring points
  • One (1) 8-bit analog-to-digital converter (0 to 5VDC)
KIT-SUS-01 StartUp Stick™ for rapid configuration. Mounting Brackets
  • Mounting brackets included
  • Custom mounting options available. Contact Bomara

 




Call Us: 1-978-452-2299
First Name:
Last Name:
Company:
Address:
Mail Stop:
City:
State (if in US):
Province/Region (if outside US):
Country:
ZIP (Postal) Code:
E-mail:
Telephone:
Fax:
Questions/Comments:
Verification:

View Full Site View Mobile Optimized