Servertech » -48 VDC Power Management » Sentry 48DCWB-08-2X100-B0NB

 Server Technology Sentry 48DCWB-08-2X100-B0NB: -48VDC remote Reboot Power Switch in a 2U 19in Rack

Discontinued - Contact Bomara for Assistance

• NEBS Level 3
• Control Via RS-232 or Via IP SSL, SSH Control
• Two 100Amp inputs and 8 individual fused 20Amp Output 25Amp TPC Fuses
• -48 VDC Power Distribution, Remote Management, Power & Environmental Monitoring



4805-XLS-16



  • Description
  • Specifications
  • Features
  • Gallery



Description for the Sentry 48DCWB-08-2X100-B0NB:

The -48VDC Sentry 48DCWB-08-2X100-BONB Intelligent PDU and Remote Power Manager minimizes the impact of locked-up routers, servers and other network devices on business-critical networks. CLECs, ILECs, ISPs and enterprises use the Sentry 48DCWB-08-2X100-BONB to manage equipment in remote sites, co-location facilities and network operation centers. The Sentry 48DCWB-08-2X100-BONB eliminates the need to dispatch a field service technician for manual intervention when devices lock-up. Using a Sentry 48DCWB-08-2X100-BONB, the network operations center can quickly restart locked-up remote network servers to ensure that the network is fully operational around the clock.

Sentry 48 VDC provides immediate operational cost savings, including:

  • Reduced field service visits
  • Improved problem/solution response time
  • Improved network availability
  • Improved facility security


Eliminate the Need for a Separate Power Distribution Panel

  • The Sentry 48DCWB-08-2X100-BONB is an intelligent unit that combines the functions of a power distribution panel and remote power management unit into a 2U 19"rack-mounted enclosure.
  • Each power output terminal connection is rated to switch 20-Amps and is protected by interchangeable TPC fuses allowing for the current rating to be adjusted onsite.


Measurement Features

  • > Use either RS-232 or TCP/IP to monitor the status of key Measurement Values, SNMP or email alerts as well as Syslog to receive an alarm when a measurement value is out of a predefined threshold


Input Feed/Outlet "On Sense" - Verifies power at each power input/outlet connection 

Load Sense - Provides an accurate, real time measurement of the current draw, in amps, for each power outlet

Environmental Sensors - Supports two external probes to measure the temperature and humidity in an equipment cabinet to identify hot spots and humidity Sentry.



Specifications for the Sentry 48DCWB-08-2X100-B0NB:

Sentry  Cabinet PDU Specifications
Item # Available Input
Voltages
Rated Amperage Low Current 
Outputs
High Current 
Outputs
Dimensions
(L x W x D)
-48VDC / 2x100A infeeds / 8x20A Outputs
48DCWB-08-2X100-B0NB
48DCXB-08-2X100-B0NB****
-48 Volt DC (100 Amp) with (2) Power Input terminal blocks (A&B)

+/- & Ground
100A (On each input) None (8) 20 Amp outputs protected with TPC fuses (25 Amp Max)*** 17" x 3.5" x 16" (431 x 89 x 406 mm) 19" standard mounting brackets
48DCWB-12-2X100-A1NB
48DCXB-12-2X100-A1NB****
-48 Volt DC (100 Amp) with (2) Power Input terminal blocks (A&B)

+/- & Ground
100A (On each input) Low Current: (8) 10A* High Current: (4) 70A* 17" x 3.5" x 16" (431 x 89 x 406 mm) 19" standard mounting brackets
*** Custom TPC Fuse values: 10, 15, 20, and 25  Amps
**** Expansion Unit
Options
EMTH-1-1 Temperature & Humidity Probe, 10"
HDW-MBXT-2U 23" Mounting Brackets
Technical Specifications
Power Input
> Qty (2) 100A power input terminal blocks (+/- & N), -48 VDC

NEBS Level 3
> GR-1089-Core> Sections 1-4,7,9, and 10GR-63-Core> Section 4ESTI > 300 019-2-1> 300 019-2-2> 300 019-2-3  

Standards
> US & Canada (cTUVus Mark) to UL 60950-1:2007 and CAN/CSA 22.2 No. 60950-1-07
> European Union (TUVgs Mark) to EN 60950-1:2006 + A11
> CE Mark
> FCC Class A, Part 15
> EMC to EN55022 Class A, EN 55024, CISPR 22 Class A

Communications
> 10/100 Base T Ethernet
> HTTP/HTTPs
> SSLv3/TLSv1
> SNMPv2/v3
> SSHv2
> Telnet
> LDAPv3/LDAPS
> TACACS+
> Serial Port Access (RJ45 and DB9)
> IPv6

RS-232 Data Format
> 1200, 2400, 4800, 9600, 19200, 38400 or 57600; 
    8 data bits, no parity; 1 stop bit

User Interface
> Command Line Interface & HTML GUI for power management and configuration 
> Telnet/ANSI/VT 100 Terminal Emulation for command-line and Pass-Thru
 




Features for the Sentry 48DCWB-08-2X100-B0NB:

Remote Power Control

Individual or group outlet remote power control to cycle power and reboot any selected server(s) or other network device(s).  Use TCP/IP (HTTP, HTTPS, SSH, Telnet, SNMP) or RS-232 to communicate with each Sentry Cabinet PDU and rectify locked-up network devices. Assign outlets to a group for control of dual-power supply servers and other gear with a single command.  Create an unlimited number of groups with any combination of outlets associated to each group. Reduce Mean Time to Repair (MTTR) a failing server by controlling individual power outlet receptacles to reboot any selected server or other device.

HTTP/HTTPs Web Configuration & Control

Use the Sentry Web interface to configure each unit, including network settings, outlet naming & grouping, SNMP traps for environmental & power thresholds and firmware updates. Also use the Web interface to control individual or group outlets and monitor key values, including amperage load(s), temperature/humidity and other environmental conditions. SSL security provides a secure HTTPs connection.

SNMP Management & Event Notification

The Sentry family of products supports the Simple Network Management Protocol (SNMP). This allows network management systems to use SNMP requests to retrieve information and control power for the individual outlets. The Sentry includes an SNMP v1 agent supporting standard MIB I and MIB II objects. A private enterprise MIB extension (Sentry3 MIB) is also supported to provide remote power control. SNMP traps can be generated for various events, including Input Current Load Thresholds (min & max), Temperature Thresholds (min & max), Humidity Thresholds (min & max), water indication, closed contacts (cabinet doors open/close), as well as notification of any time an outlet status is changed (on/off).

Rack Mount Enclosure

"Horizontal" rack-mount enclosures are 17" wide and include standard mounting brackets for 19" cabinet rails.  23" brackets also available.

Secure Access - SSH or SSL Protection

Secure Shell (SSH), known as Secure Socket Shell, is a Unix-based command interface and protocol for securely getting access to a remote device.  Sentry supports SSHv2. Secure Sockets Layer (SSL) is a commonly-used protocol for managing the security of a message transmission on the Internet. SSL is an integral part of most Web browsers (clients) and Web servers.  Sentry supports SSLv3/TLSv1.

Firmware Flash Upgradable

Access new firmware updates via FTP for new firmware features and code releases. An update to the firmware does not affect the status of the power outlets.

LDAP/LDAPS

The sentry family of products supports Lightweight Directory Access Protocol (LDAP) Version 3 including LDAPS (LDAP over TSL/SSL). This support enable authentication with LDAP servers; user accounts do not need to be individually created locally on each Sentry device.
This allows administrators to pre-define and configure (in each Sentry product, and in the LDAP server) a set of necessary LDAP groups, and access rights for each. User's access rights can then be assigned or revoked simply by making the user a member of one or more pre-defined Sentry LDAP groups. User account can be added, deleted, or changed in the LDAP server without any changes on individual Sentry products.
Sentry LDAP support has been tested in the following environments:
     - Microsoft Active Directory (MSAD)
     - Novell eDirectory (eDir)
     - Open LDAP

Load Sense

Individual input current monitoring ("Load Sense") provides real-time power measurement of the load in amps on each power inlet, accessible via firmware interface.

RS-232 Control

Serial control via any device with a bi-directional serial port, including a PC, laptop, KVM switch, Console Port Access switch, or terminal server.

24-Character Outlet Receptacle Names

Use the firmware interface (Web or serial) to edit individual outlet receptacles. Identify each receptacle with the device's serial number, IP address, asset allocation #, department or any other method to individually name outlets.

 