Bomara Home » Server Technology » Smart IP PDU » Smart CS-12HD2/E Dual 208-240V with PIPS

 Smart CS-12HD2/E: Dual 208-240V with PIPS
  Sentry Smart horizontal PDU with dual infeeds and PIPS (Per Inlet Power Sensing)


CS-12HD2G454A3_outlets



  • Description
  • Specifications
  • Gallery

The Sentry CS-12HD2/E products provide twelve IEC 60320 C19 outlets for high density applications found in data center cabinets. Smart Cabinet Distribution Units (CDU) provide reliable single phase power distribution combined with local and remote power monitoring and environmental monitoring via IP. 

Increasing power demands and density in the equipment cabinet requires new functionality from your cabinet PDU.  The Sentry Cabinet PDU product family uniquely meets these demands.

This Sentry PIPS CDU provides the ability to provide power monitoring per inlet/infeed. Power information per infeed includes current, voltage, power, apparent power, crest factor, reactance, power factor and accumulated energy.

This information replaces branch circuit monitoring devices typically installed in the power distribution panel or remote power panel (RPP) with higher accuracy and lower cost monitoring of each circuit attached to the CDU.

Combine the Sentry PIPS Smart Cabinet PDU with the Sentry Power Manager software tool to gain power usage information across multiple Cabinet PDU's individual IP address.

230 V products include a EN 60950-1:2001 certification.

 

Remote Power Monitoring

Monitor input power via IP or serial interface.

HTTP/HTTPs Web Configuration & Control

Use the Sentry Web interface to configure each unit's network settings. SNMP traps for environmental & power thresholds and firmware updates. Also use the Web interface to monitor key values, including amperage load(s), temperature/humidity and other environmental conditions. SSL security provides a secure HTTPs connection.

SNMP Management & Event Notification

The Sentry family of products supports the Simple Network Management Protocol (SNMP). This allows network management systems to use SNMP requests to retrieve information such as input power, temperature and humidity. The Sentry includes an SNMP v1 agent supporting standard MIB I and MIB II objects. A private enterprise MIB extension (Sentry3 MIB) is also supported to provide remote power control. SNMP traps can be generated for various events, including Input Current Load Thresholds (min & max), Temperature Thresholds (min & max), Humidity Thresholds (min & max), water indication, and closed contacts (cabinet doors open/close).

2U Enclosure

A horizontal enclosure that occupies 2U horizontal rack space in the equipment cabinet. It typically mounts on the back of a 19 or 23 inch rack.

Secure Access - SSH or SSL Protection

Secure Shell (SSH), known as Secure Socket Shell, is a Unix-based command interface and protocol for securely getting access to a remote device.  Sentry supports SSHv2. Secure Sockets Layer (SSL) is a commonly-used protocol for managing the security of a message transmission on the Internet. SSL is an integral part of most Web browsers (clients) and Web servers.  Sentry supports SSLv3/TLSv1.

Integrated Temp/Humidity Probe Support

Two (2) RJ-style connectors located on the face panel of the PDU's enclosure provide support for two (2) Integrated Temperature & Humidity Probes with ten-foot (10') cables provide real-time measurements in the data center cabinet.

Firmware Flash Upgradable

Access new firmware updates via FTP for new firmware features and code releases. An update to the firmware does not affect the status of the power outlets.

LDAP/LDAPS

The sentry family of products supports Lightweight Directory Access Protocol (LDAP) Version 3 including LDAPS (LDAP over TSL/SSL). This support enable authentication with LDAP servers; user accounts do not need to be individually created locally on each Sentry device.
This allows administrators to pre-define and configure (in each Sentry product, and in the LDAP server) a set of necessary LDAP groups, and access rights for each. User's access rights can then be assigned or revoked simply by making the user a member of one or more pre-defined Sentry LDAP groups. User account can be added, deleted, or changed in the LDAP server without any changes on individual Sentry products.
Sentry LDAP support has been tested in the following environments:
  - Microsoft Active Directory (MSAD)
  - Novell eDirectory (eDir)
  - Open LDAP

RS-232 Control

Serial control via any device with a bi-directional serial port, including a PC, laptop, KVM switch, Console Port Access switch, or terminal server.


Sentry  Cabinet PDU Specifications
Item # Available Input
Voltages
Rated Amperage Available Input Cord** Outlets Dimensions
(L x H x D)
CS-12HD2/E 200-240V with PIPS
CS-12HD2G454A3
CL-12HD2G454A3*
208-240V
50/60 Hz
20A (2) NEMA L6-20P Plug, 10'(3m) Cords (12) IEC 60320/C19 3.50 x 17.20 x 10.00 in.
(89 x 437 x 254 mm)
CS-12HD2C454A3
CL-12HD2C454A3*
208-240V
50/60 Hz
30A (2) NEMA L6-30P Plug, 10'(3m) Cords (12) IEC 60320/C19 3.50 x 17.20 x 10.00 in.
(89 x 437 x 254 mm)
CS-12HDEJ454A3
CL-12HDEJ454A3*
230V
50/60Hz
16A (2) IEC Blue 2P+G Plug, 10'(3m) Cords (12) IEC 60320/C19 3.50 x 17.20 x 10.00 in.
(89 x 437 x 254 mm)
CS-12HDEK454A3
CL-12HDEK454A3*
230V
50/60Hz
32A (2) IEC Blue 2P+G Plug, 10'(3m) Cords (12) IEC 60320/C19 3.50 x 17.20 x 10.00 in.
(89 x 437 x 254 mm)
* CL refers to the Expansion Module
**Click here to view additional information on Power Cords and Cables
Additional Features and Specifications
Standards
> cTUVus - UL 60950-1-2003
> CAN/CSA 22.2 No. 60950-1:2003
> TUVGS - EN 60950-1:2001
> FCC Class A, Part 15
> CE
> EMC-EN 55022 Class A, EN 55024

Communications
> 10/100 BaseT Ethernet
> HTTP/HTTPS
> SSLv3/TLSv1
> SNMPv2
> SSHv2
> Telnet
> LDAPv3 and LDAPS
> TACACS+
> RADIUS
> RS-232 (Serial)

Branch Circuit Protection
> Compliant to UL 60950-1

Accessories
> Temperature & Humidity Probe 
    - EMTH-1-1 Temperature & Humidity Probe, 10 ft (3 m)
> EMCU-1-1B add 2 additional Temperature & Humidity ports, 4 contact-closure monitoring ports and 1 water sensor port



   Additional Ordering Information


Part Number Input Output
Master Expansion Rating, North America GS Input Type Output Rating North America GS Outlet: North America / GS Outlet Type Branch Circuit: North America / GS
CS-12HD2G454A3 CL-12HD2G454A3 208-240V, 50/60Hz; 2x 16A   NEMA L6-20P 208-240V, 50/60Hz; A, B <= 16A   <= 16A/ IEC 60320 C19 <= 16A/
CS-12HD2C454A3 CL-12HD2C454A3 208-240V, 50/60Hz; 2x 24A   NEMA L6-30P 208-240V, 50/60Hz; A, B <= 24A   <= 16A/ IEC 60320 C19 <= 16A/
CS-12HDEJ454A3 CL-12HDEJ454A3   230V, 50/60Hz; 2x 16A IEC 60320 C20 Inlet   230V, 50/60Hz; A, B <= 16A /<= 16A IEC 60320 C19 /<= 16A
CS-12HDEK454A3 CL-12HDEK454A3   230V, 50/60Hz; 2x 32A IEC 60309 32A   230V, 50/60Hz; A, B <= 32A /<= 16A IEC 60320 C19 /<= 16A



   Additional Features and Specifications

Standards
> cTUVus - UL 60950-1-2003
> CAN/CSA 22.2 No. 60950-1:2003
> TUVGS - EN 60950-1:2001
> FCC Class A, Part 15
> CE
> EMC-EN 55022 Class A, EN 55024

Communications
> 10/100 BaseT Ethernet
> HTTP/HTTPS
> SSLv3/TLSv1
> SNMPv2
> SSHv2
> Telnet
> LDAPv3 and LDAPS
> TACACS+
> RADIUS
> RS-232 (Serial)

Branch Circuit Protection
> Compliant to UL 60950-1

Accessories
> Temperature & Humidity Probe 
    - EMTH-1-1 Temperature & Humidity Probe, 10 ft (3 m)
> EMCU-1-1B add 2 additional Temperature & Humidity ports, 4 contact-closure monitoring ports and 1 water sensor port

 