 Smart CS-24V4: 400V 16/32A 3 phase 18xC13 & 6xC19
  3-Phase power distribution, 24 outlets with LED input current displays and IP monitoring; high-density.


CS-24V_C13lC19_-3Ph



  • Description
  • Specifications
  • Gallery

The three phase Smart Cabinet PDU (power distribution unit) delivers reliable power distribution, local power monitoring via LEDs, power monitoring via IP and environmental (temperature & humidity) monitoring via IP.   

Increasing power demands and density in the equipment cabinet requires new functionality from your cabinet PDU.  The Sentry Cabinet PDU product family uniquely meets these demands. 

The Sentry Cabinet Power Distribution Unit (Cabinet PDU) is an intelligent PDU with local LED input current monitoring, allowing network engineers to utilize the Cabinet PDU's True RMS Power Monitor to precisely measure the current (in amps) that network devices are drawing on the power circuit. As new equipment units are added to the power drop, immediately observe its impact on the cumulative current draw. This allows the engineer to safely load each circuit to its maximum allowable load capacity without the danger of overloading the power circuit.  

The Cabinet PDU meets new UL 60950-1 Branch Circuit Protection requirements. Each branch circuit utilizes a Bussman® SC fuse as an Overcurrent Protection Device (OCPD).  Now you can safely run 30-amp power drops to your server cabinet where individual outlet receptacles have lower output ratings (i.e., 20-amps).

400 V products include a EN 60950-1:2001 certification.

Designated Smart Products are linkable.



Remote Power Monitoring

Monitor input power via IP or serial interface.

HTTP/HTTPs Web Configuration & Control

Use the Sentry Web interface to configure each unit's network settings. SNMP traps for environmental & power thresholds and firmware updates. Also use the Web interface to monitor key values, including amperage load(s), temperature/humidity and other environmental conditions. SSL security provides a secure HTTPs connection.

SNMP Management & Event Notification

The Sentry family of products supports the Simple Network Management Protocol (SNMP). This allows network management systems to use SNMP requests to retrieve information such as input power, temperature and humidity. The Sentry includes an SNMP v1 agent supporting standard MIB I and MIB II objects. A private enterprise MIB extension (Sentry3 MIB) is also supported to provide remote power control. SNMP traps can be generated for various events, including Input Current Load Thresholds (min & max), Temperature Thresholds (min & max), Humidity Thresholds (min & max), water indication, and closed contacts (cabinet doors open/close).

Add a Second Tower

Connect an Expansion Cabinet PDU to this Smart Cabinet PDU to control two power input circuits and monitor power in the Data Center cabinet(individual or groups) under 1 IP address - our exclusive strategy for managing dual power-supply servers.

Zero U Enclosure

A vertical enclosure that occupies Zero Vertical U of rack space in the equipment cabinet. It mounts on the back rails or in the cavity space of the cabinet.

Secure Access - SSH or SSL Protection

Secure Shell (SSH), known as Secure Socket Shell, is a Unix-based command interface and protocol for securely getting access to a remote device.  Sentry supports SSHv2. Secure Sockets Layer (SSL) is a commonly-used protocol for managing the security of a message transmission on the Internet. SSL is an integral part of most Web browsers (clients) and Web servers.  Sentry supports SSLv3/TLSv1.

Integrated Temp/Humidity Probe Support

Two (2) RJ-style connectors located on the face panel of the PDU's enclosure provide support for two (2) Integrated Temperature & Humidity Probes with ten-foot (10') cables provide real-time measurements in the data center cabinet.

Firmware Flash Upgradable

Access new firmware updates via FTP for new firmware features and code releases. An update to the firmware does not affect the status of the power outlets.

LDAP/LDAPS

The sentry family of products supports Lightweight Directory Access Protocol (LDAP) Version 3 including LDAPS (LDAP over TSL/SSL). This support enable authentication with LDAP servers; user accounts do not need to be individually created locally on each Sentry device.
This allows administrators to pre-define and configure (in each Sentry product, and in the LDAP server) a set of necessary LDAP groups, and access rights for each. User's access rights can then be assigned or revoked simply by making the user a member of one or more pre-defined Sentry LDAP groups. User account can be added, deleted, or changed in the LDAP server without any changes on individual Sentry products.
Sentry LDAP support has been tested in the following environments:
  - Microsoft Active Directory (MSAD)
  - Novell eDirectory (eDir)
  - Open LDAP

RS-232 Control

Serial control via any device with a bi-directional serial port, including a PC, laptop, KVM switch, Console Port Access switch, or terminal server.


Sentry  Cabinet PDU Specifications
Item # Available Input
Voltages
Rated Amperage Available Input Cord*** Outlets Dimensions
(L x W x D)
CS-24V4 (C13/C19)-3Ph
CS-24V4-P16MA
CL-24V4-P16MA*
3-Phase Wye, 400V
50/60Hz
16A IEC 60309
Cord Set, 10 ft (3m)
(18)  IEC 60320/C13
(6) IEC 60320/C19
69"x1.75"x2.25"
(1752x44x57mm)
CS-24V4-P32MA
CL-24V4-P32MA*
3-Phase Wye, 400V
50/60Hz
32A IEC 60309
Cord Set, 10 ft (3m)
(18)  IEC 60320/C13
(6) IEC 60320/C19
69"x1.75"x2.25"
(1752x44x57mm)
*CL refers to the Module
**Please note that the depth of these enclosures are 3.00" deep at the placement for the fuse retractors
**Click here to view additional information on Power Cords and Cables



  Additional Ordering Information


Part Number Input Output
Master Expansion Rating, North America GS Input Type Output Rating North America GS Outlet: North America GS Outlet Type Branch Circuit: North America / GS Phase: North America / GS
C-24V4-P16MA     230/400V 3W+N+PE, 50/60Hz; 16A IEC 60309 16A   230V, 50/60Hz; <= 48A   6xC19 <= 16A ea ch, 18xC13 <= 10A each IEC 60320 C13 / C19 / L1a , L1b, L2a , L2b, L3a , L3b <= 16A / L1, L2, L3 <= 16A
C-24V4-P32MA     230/400V 3W+N+PE, 50/60Hz; 32A IEC 60309 32A   230V, 50/60Hz; <= 96A   6xC19 <= 16A ea ch, 18xC13 <= 10A each IEC 60320 C13 / C19 / L1a , L1b, L2a , L2b, L3a , L3b <= 16A / L1, L2, L3 <= 32A
CS-24V4-P16MA CL-24V4-P16MA   230/400V 3W+N+PE, 50/60Hz; 16A IEC 60309 16A   230V, 50/60Hz; <= 48A   6xC19 <= 16A ea ch, 18xC13 <= 10A each IEC 60320 C13 / C19 / L1a , L1b, L2a , L2b, L3a , L3b <= 16A / L1, L2, L3 <= 16A
CS-24V4-P32MA CL-24V4-P32MA   230/400V 3W+N+PE, 50/60Hz; 32A IEC 60309 32A   230V, 50/60Hz; <= 96A   6xC19 <= 16A ea ch, 18xC13 <= 10A each IEC 60320 C13 / C19 / L1a , L1b, L2a , L2b, L3a , L3b <= 16A / L1, L2, L3 <= 32A
CS-24V52311A1 CL-24V52311A1 240/416V 3W+N+PE, 50/60Hz; 16A   NEMA L22-20P 240V, 50/60Hz; <= 48A   6xC19 <= 16A ea ch, 18xC13 <= 12A each   IEC 60320 C13 / C19 L1a , L1b, L2a , L2b, L3a , L3b <= 20A / L1, L2, L3 <= 16A /
CS-24V53311A1
Replaced by C1S24VS-5NFA11F2
CL-24V53311A1
240/416V 3W+N+PE, 50/60Hz; 16A   IEC 60309 16A 240V, 50/60Hz; <= 48A   6xC19 <= 16A ea ch, 18xC13 <= 12A each   IEC 60320 C13 / C19 L1a , L1b, L2a , L2b, L3a , L3b <= 20A / L1, L2, L3 <= 16A /
CS-24V54311A1
Replaced by C1S24VS-5PFA11F2
CL-24V54311A1 240/416V 3W+N+PE, 50/60Hz; 24A   IEC 60309 24A 240V, 50/60Hz; <= 72A   6xC19 <= 16A ea ch, 18xC13 <= 12A each   IEC 60320 C13 / C19 L1a , L1b, L2a , L2b, L3a , L3b <= 20A / L1, L2, L3 <= 24A /
CS-24V5Z311A1
Replaced by C1S24VS-5CFA11F2
CL-24V5Z311A1 240/416V 3W+N+PE, 50/60Hz; 24A   NEMA L22-30P 240V, 50/60Hz; <= 72A   6xC19 <= 16A ea ch, 18xC13 <= 12A each   IEC 60320 C13 / C19 L1a , L1b, L2a , L2b, L3a , L3b <= 20A / L1, L2, L3 <= 24A /
CS-24V4J313A1 CL-24V4J313A1   230/400V 3W+N+PE, 50/60Hz; 16A IEC 60309 16A   230V, 50/60Hz; <= 48A   6xC19 <= 16A ea ch, 18xC13 <= 10A each IEC 60320 C13 / C19 / L1a , L1b, L2a , L2b, L3a , L3b <= 16A / L1, L2, L3 <= 16A
CS-24V4K313A1 CL-24V4K313A1   230/400V 3W+N+PE, 50/60Hz; 32A IEC 60309 32A   230V, 50/60Hz; <= 96A   6xC19 <= 16A ea ch, 18xC13 <= 10A each IEC 60320 C13 / C19 / L1a , L1b, L2a , L2b, L3a , L3b <= 16A / L1, L2, L3 <= 32A
CS-24V52313A1 CL-24V52313A1 240/416V 3W+N+PE, 50/60Hz; 16A   NEMA L22-20P 240V, 50/60Hz; <= 48A   6xC19 <= 16A ea ch, 18xC13 <= 12A each   IEC 60320 C13 / C19 L1a , L1b, L2a , L2b, L3a , L3b <= 20A / L1, L2, L3 <= 16A /
CS-24V53313A1 CL-24V53313A1 240/416V 3W+N+PE, 50/60Hz; 16A   IEC 60309 16A 240V, 50/60Hz; <= 48A   6xC19 <= 16A ea ch, 18xC13 <= 12A each   IEC 60320 C13 / C19 L1a , L1b, L2a , L2b, L3a , L3b <= 20A / L1, L2, L3 <= 16A /
CS-24V54313A1 CL-24V54313A1 240/416V 3W+N+PE, 50/60Hz; 24A   IEC 60309 24A 240V, 50/60Hz; <= 72A   6xC19 <= 16A ea ch, 18xC13 <= 12A each   IEC 60320 C13 / C19 L1a , L1b, L2a , L2b, L3a , L3b <= 20A / L1, L2, L3 <= 24A /
CS-24V5Z313A1 CL-24V5Z313A1 240/416V 3W+N+PE, 50/60Hz; 24A   NEMA L22-30P 240V, 50/60Hz; <= 72A   6xC19 <= 16A ea ch, 18xC13 <= 12A each   IEC 60320 C13 / C19 L1a , L1b, L2a , L2b, L3a , L3b <= 20A / L1, L2, L3 <= 24A /


Part Number Description
CS-24V53311 Smart CDU, 0U, 24 x IEC C13 outlets, 3 x LED amp meters, 240/415V 3-Phase Wye, 20A IEC 60309 (5-pin Pin/Sleeve, Red, 6 O clock Ground) Connector, BoEom/Front Cord Entry, 3m (10 ) Cord, Fused Branch Circuit ProtecFon, w/ 2 x
Temp/Humid Capable
CL-24V53311 Smart CDU (Expansion Unit), 0U, 24 x IEC C13 outlets, 3 x LED amp meters, 240/415V 3-Phase Wye, 20A IEC 60309 (5-pin Pin/Sleeve, Red, 6 O clock Ground) Connector, BoEom/Front Cord Entry, 3m (10 ) Cord, Fused Branch Circuit Protection
CS-24V5Z311 Smart CDU, 0U, 24 x IEC C13 outlets, 3 x LED amp meters, 240/415V 3-Phase Wye, 30A NEMA L22-30P Connector, BoEom/Front Cord Entry, 3m (10 ) Cord, Fused Branch Circuit ProtecFon, w/ 2 x Temp/Humid Capable
CL-24V5Z311 Smart CDU (Expansion Unit), 0U, 24 x IEC C13 outlets, 3 x LED amp meters, 240/415V 3-Phase Wye, 30A NEMA L22-30P Connector, Bottom/Front Cord Entry, 3m (10?) Cord, Fused Branch Circuit Protection

 

  Additional Features and Specifications

Standards
> TUVGS - EN 60950-1:2001
> FCC Class A, Part 15
> CE
> EMC-EN 55022 Class A, EN 55024

Communications
> 10/100 BaseT Ethernet
> HTTP/HTTPS
> SSLv3/TLSv1
> SNMPv2
> SSHv2
> Telnet
> LDAPv3/LDAPS
> TACACS+
> RADIUS
> RS-232 (Serial)

Branch Circuit Protection

> Compliant to UL 60905-1

Accessories
> Temperature & Humidity Probe 
    - EMTH-1-1 Temperature & Humidity Probe, 10 ft (3 m)
    - EMCU-1-1 add 2 additional Temperature & Humidity ports, 4 contact-closure monitoring ports and 
      1 water sensor port

 