Bomara Home » Server Technology » Smart IP PDU » Smart CS-36V2: 208-240V 1-Phase 60A 30xC13 & 6xC19 with PIPS

 Smart CS-36V2QE25D4: 208-240V 1-Phase 60A 30xC13 & 6xC19 with PIPS
  PIPS, Per Inlet Power Sensing in a high density 1Phase 60A solution.


All parts on this page have been discontinued. Contact Bomara for a replacement.
CS-36V2QE25D4_master



  • Description
  • Specifications
  • Gallery

This Sentry PIPS CDU combines all of the features of a Smart CDU with the ability to provide power monitoring per inlet/infeed. Power information per infeed includes current, voltage, power, apparent power, crest factor, reactance, power factor and accumulated energy. This information replaces branch circuit monitoring devices typically installed in the power distribution panel or remote power panel (RPP) with higher accuracy and lower cost monitoring of each circuit attached to the CDU.

Combine the Sentry PIPS Smart Cabinet PDU with the Sentry Power Manager (SPM) software tool to gain power usage information across multiple Cabinet PDU's individual IP address.

This Smart cabinet PDU delivers reliable power distribution, local power monitoring via LEDs, power monitoring via IP and environmental (temperature & humidity) monitoring via IP.   

Increasing power demands and density in the equipment cabinet requires new functionality from your cabinet PDU.  The Sentry cabinet PDU product family uniquely meets these demands. 

The Sentry Cabinet Power Distribution Unit (cabinet PDU) is an intelligent PDU with local LED input current monitoring, allowing network engineers to utilize the cabinet PDU's True RMS Power Monitor to precisely measure the current (in amps) that network devices are drawing on the power circuit. As new equipment units are added to the power drop, immediately observe its impact on the cumulative current draw. This allows the engineer to safely load each circuit to its maximum allowable load capacity without the danger of overloading the power circuit.   

The cabinet PDU meets new UL 60950-1 Branch Circuit Protection requirements. 




Remote Power Monitoring

Monitor input power via IP or serial interface.

HTTP/HTTPs Web Configuration & Control

Use the Sentry Web interface to configure each unit's network settings. SNMP traps for environmental & power thresholds and firmware updates. Also use the Web interface to monitor key values, including amperage load(s), temperature/humidity and other environmental conditions. SSL security provides a secure HTTPs connection.

SNMP Management & Event Notification

The Sentry family of products supports the Simple Network Management Protocol (SNMP). This allows network management systems to use SNMP requests to retrieve information such as input power, temperature and humidity. The Sentry includes an SNMP v1 agent supporting standard MIB I and MIB II objects. A private enterprise MIB extension (Sentry3 MIB) is also supported to provide remote power control. SNMP traps can be generated for various events, including Input Current Load Thresholds (min & max), Temperature Thresholds (min & max), Humidity Thresholds (min & max), water indication, and closed contacts (cabinet doors open/close).

Add a Second Tower

Connect an Expansion Cabinet PDU to this Smart Cabinet PDU to control two power input circuits and monitor power in the Data Center cabinet (individual or groups) under 1 IP address - our exclusive strategy for managing dual power-supply servers.

Zero U Enclosure

A vertical enclosure that occupies Zero Vertical U of rack space in the equipment cabinet. It mounts on the back rails or in the cavity space of the cabinet.

Secure Access - SSH or SSL Protection

Secure Shell (SSH), known as Secure Socket Shell, is a Unix-based command interface and protocol for securely getting access to a remote device.  Sentry supports SSHv2. Secure Sockets Layer (SSL) is a commonly-used protocol for managing the security of a message transmission on the Internet. SSL is an integral part of most Web browsers (clients) and Web servers.  Sentry supports SSLv3/TLSv1.

Integrated Temp/Humidity Probe Support

Two (2) RJ-style connectors located on the face panel of the PDU's enclosure provide support for two (2) Integrated Temperature & Humidity Probes with ten-foot (10') cables provide real-time measurements in the data center cabinet.

Firmware Flash Upgradable

Access new firmware updates via FTP for new firmware features and code releases. An update to the firmware does not affect the status of the power outlets.

LDAP/LDAPS

The sentry family of products supports Lightweight Directory Access Protocol (LDAP) Version 3 including LDAPS (LDAP over TSL/SSL). This support enable authentication with LDAP servers; user accounts do not need to be individually created locally on each Sentry device.
This allows administrators to pre-define and configure (in each Sentry product, and in the LDAP server) a set of necessary LDAP groups, and access rights for each. User's access rights can then be assigned or revoked simply by making the user a member of one or more pre-defined Sentry LDAP groups. User account can be added, deleted, or changed in the LDAP server without any changes on individual Sentry products.
Sentry LDAP support has been tested in the following environments:
  - Microsoft Active Directory (MSAD)
  - Novell eDirectory (eDir)
  - Open LDAP

RS-232 Control

Serial control via any device with a bi-directional serial port, including a PC, laptop, KVM switch, Console Port Access switch, or terminal server.


Sentry  CDU Specifications
Item # Available Input
Voltages
Rated Amperage Available Input Cord*** Outlets Dimensions
(L x W x D)**
PIPS CS-36V2/VE
CS-36V2QE25D4
CL-36V2QE25D4*
208-240V
50/60Hz
 60A IEC Blue 6hr 2P+G Plug, 10'(3m), Bottom/Frt Cord (30) IEC 60320/C13
(6) IEC 60320/C19
73.0 x 1.75 x 3.50 in.
(1854 x 44 x 89 mm)
* CL part numbers refer to the Expansion CDU
** 2.25 in. (57 mm) depth at the outlets
***Click here to view additional information on Power Cords and Cables
Additional Features and Specifications
Standards
> US and Canada (cTUVus Mark) to UL 60950-1:2003 and CAN/CSA 22.2 No. 60950-1-03 
> FCC Class A, Part 15
> EMC-EN 55022 Class A, EN 55024, CISPR 22 Class A

Communications
> 10/100 BaseT Ethernet
> HTTP/HTTPS
> SSLv3/TLSv1
> SNMPv2
> SSHv2
> Telnet
> LDAPv3 and LDAPS
> TACACS+
> RADIUS
> RS-232 (Serial)

Branch Circuit Protection
> Compliant to UL 60950-1

Accessories
> Temperature & Humidity Probe 
    - EMTH-1-1 Temperature & Humidity Probe, 10 ft (3 m)
    - EMCU-1-1B add 2 additional Temperature & Humidity ports, 4 contact-closure monitoring ports and 
      1 water sensor port

 