Server Technology Products » Switch Rack PDU Products » CWG-16HEA454

 Server Technology CWG-16HEA454 & CWG-16HEA454:
   Switched 1 Phase PDU POPS CWG-16H2/E 3.3kW - 7.3kW (16) C13 outlets

All products here have been discontinued. Contact Bomara for a replacement

• PIPS PDU: Per-Inlet power Sensing
• POPS PDU: Per-Outlet Power Sensing


The Server Technology® Switched POPS PDU provides control of outlet power and local LED input current monitoring, allowing IT personnel to determine safe levels of loading on a perphase basis while installing equipment into the rack/cabinet. The integral PIPS® and POPS® technology provides accurate measurement of current (billing-grade), voltage, active power, apparent power, power factor, crest factor, and accumulated energy at the input and at each output. These power data points, along with temperature and humidity measurements (provided via optional probes), are accessible through the built-in Web and CLI interfaces as well as through SNMP. The Switched POPS “Master” PDU can be connected to a Switched POPS “Link” PDU to extend the network access to the redundant or secondary power feed.


  • Models Information
  • Additional Specifications
  • Mechanical Drawing
  • Features



Models and Specifications for the CWG-16HEA454 & CXG-16HEA454:


Model Description
CWG-16HEA454 Switched PIPS/POPS PDU, Per Outlet Power Sensing, 2U, 16 x IEC C13 Outlets, Input Amp Meter, 230V 16A w/ IEC C20 Inlet (Front Cord Entry), 20 A Circuit Breakers, (2) Temperature/Humidity Sensor Capable (Input power cord sold separately).
CXG-16HEA454 Switched PIPS/POPS PDU (Expansion Unit), Per Outlet Power Sensing, 2U, 16 x IEC C13 Outlets, Input Amp Meter, 230V 16A w/ IEC C20 Inlet (Front Cord Entry), 20 A Circuit Breakers, (Input power cord sold separately)



Additional Specifications for the CWG-16HEA454 & CXG-16HEA454:


Inputs
Input Voltage: 230VAC 1 Phase
Input Plug: IEC C20 200-240V Inlet *
Input Current: 16
Input Current Rated: 16
Outputs
Connector: (16) x IEC 60320/C13
North American Rating (C13): ≤ 12A @208V L-N (15A Peak)
Global Rating (C13): ≤ 10A @230V L-N
Locking outlets provide high-retention even for non-locking cords.
Branch Circuit Protection
UL489 compliant 2-pole, 20A trip circuit breakers, two (2) branches, rating: ≤ 16A @220-240V
Physical
Dimensions: 3.5 (89.0 mm) tall x 17.2 (437.0 mm) wide x 7.1 (181.0 mm) deep
Environmental
Operating Environment: 32°F to 122°F / 0°C to 50 °C | 8%RH to 90%RH non-condensing | 6,500ft/2km elevation
Storage Environment: -40°F to 185°F / -40°C to 85°C | 8%RH to 90%RH non-condensing | 50,000ft/15km elevation
Quiescent / Unloaded Power Draw: <10W for all configurations
Communications & Security
10/100 Mbps Ethernet (RJ-45 connector), RS-232 serial (RJ-45 connector) Two (2) temperature/humidity sensor inputs (4P4C), Link port (RJ-12) - {also on Link PDU} Web-browser GUI and command-line interface (CLI): HTTP/HTTPS, TLSv1, SSHv2, Telnet, SNMPv2c and v3 (GET, SET, Traps), IPv4 and IPv6, LDAPv3/LDAPS, TACACS+, RADIUS, FTP/SFTP
Certifications
North American: cTUVus Mark to UL 60950-1:2007 and CAN/CSA 22.2 No. 60950-1-07 + A1:2011
EMC to EN 55022 Class A, EN 55024, CISPR 22 Class A
FCC Class A, Part 15
Global: TUV T-Mark to EN 60950-1:2006 + A11 + A1 + A12
EMC to EN 55022 Class A, EN 55024, CISPR 22 Class A
CE Mark
RoHS/WEEE
Measurement Accuracy
Input Measurement Accuracy: LED Current = ± 10% at 0.1 amp (0.3 - 9.9 amps) and 1 amp (> 9.9 amps) resolution
GUI Current = ± 1% at 0.01 amp resolution (above 0.25 amp)
Voltage = ± 1% at 0.1 volt resolution (nominal ± 10%)
Active Power = ± 1% at 1 watt resolution
Apparent Power = ± 1% at 1 volt-amp resolution
Power Factor = ± 3% at 0.01 resolution
Crest Factor = ± 10% at 0.1 resolution
Energy = ± 1% at 0.1 kilowatt-hour resolution
Output Measurement Accuracy: GUI Current = ± 1% at 0.01 amp resolution (above 0.15 amp)
Voltage = ± 1% at 0.1 volt resolution (nominal ± 10%)
Active Power = ± 1% at 1 watt resolution
Apparent Power = ± 1% at 1 volt-amp resolution
Power Factor = ± 3% at 0.01 resolution
Crest Factor = ± 10% at 0.1 resolution
Energy = ± 1% at 1 watt-hour resolution
Optional Accessories
EMTH-1-1 Combination Temperature/Humidity Probe, 10ft (3m)
EMCU-1-1B Environmental Monitor adding:
- Two (2) EMTH-1-1 temperature/humidity ports (one probe included)
- One (1) EMWS-1-1 water sensor port (probe sold separately)
- Four (4) dry contact (NO/NC) monitoring points
- One (1) 8-bit analog-to-digital converter (0 to 5VDC)

KIT-STEYE-01 or -10 provides access to key metrics through Bluetooth
SPM (Sentry® Power Manager):
- Monitor and manage multiple PDUs from a single point
- Monitor and manage alarm conditions
- Create reports and trends on stored data
- Analyze power usage per phase
- Optional appliance or virtual version
- Vmware Ready2

Mounting Brackets:
- Buttons (KIT-0020) included for tool-less mounting (see diagram)
- See the Mounting Bracket Guide for further suggestions
- Custom mounting options available. Contact Bomara for non-locking cords
- Ezip
- Cable Sleeve
Warranty:
Server Technology offers a standard 2-year limited parts & labor warranty. Extended support is available at the time of purchase. Please contact Bomara for more information.

 



Mechanical Drawing for the CWG-16HEA454 & CXG-16HEA454:

CWG-16HEA454_005



Features for the CWG-16HEA454 & CXG-16HEA454: