Bomara Home » Server Technology Products » Switched PDU Products » CWG-24V0A415C1

 Server Technology CWG-24V0A415C1: Switched 1 Phase PDU 208VAC C20 Input, (18) C13 & (6) C19 Output

All products here have been discontinued. Contact Bomara for a replacement

CWG-24V0A415C1 (Master)
CXG-24V0A415C1 (Expansion)





Inputs
Input Voltage: 208VAC 1 Phase
Input Plug: IEC C20 200-240V Inlet *
Input Current: 16
Input Current Rated: 16
Outputs
Connector: (18) x IEC 60320/C13
North American Rating (C13): ≤ 12A @208V L-L (15A Peak)
   
Global Rating (C13): ≤ 10A @230V L-L
   
Connector: (6) x IEC 60320/C19
North American Rating (C19): ≤ 16A @208V L-L (20A Peak)
   
Locking outlets provide high-retention even for non-locking cords.
Branch Circuit Protection
UL489 compliant 2-pole, 20A trip circuit breakers, two (2) branches, rating: ≤ 16A @208-240V
Physical
Dimensions: 64.0 (1626.0 mm) tall x 1.75 (45.0 mm) wide x 3.5 (89.0 mm) deep
Environmental
Operating Environment: 32°F to 122°F / 0°C to 50 °C | 8%RH to 90%RH non-condensing | 6,500ft/2km elevation
Storage Environment: -40°F to 185°F / -40°C to 85°C | 8%RH to 90%RH non-condensing | 50,000ft/15km elevation
Quiescent / Unloaded Power Draw: <10W for all configurations
Communications & Security
10/100 Mbps Ethernet (RJ-45 connector), RS-232 serial (RJ-45 connector) Two (2) temperature/humidity sensor inputs (4P4C), Link port (RJ-12) - {also on Link PDU} Web-browser GUI and command-line interface (CLI): HTTP/HTTPS, TLSv1, SSHv2, Telnet, SNMPv2c and v3 (GET, SET, Traps), IPv4 and IPv6, LDAPv3/LDAPS, TACACS+, RADIUS, FTP/SFTP
Certifications
North American: cTUVus Mark to UL 60950-1:2007 and CAN/CSA 22.2 No. 60950-1-07 + A1:2011
EMC to EN 55022 Class A, EN 55024, CISPR 22 Class A
FCC Class A, Part 15
Global: TUV T-Mark to EN 60950-1:2006 + A11 + A1 + A12
EMC to EN 55022 Class A, EN 55024, CISPR 22 Class A
CE Mark
RoHS/WEEE
Measurement Accuracy
Input Measurement Accuracy: LED Current = ± 10% at 0.1 amp (0.3 - 9.9 amps) and 1 amp (> 9.9 amps) resolution
GUI Current = ± 1% at 0.01 amp resolution (above 0.25 amp)
Voltage = ± 1% at 0.1 volt resolution (nominal ± 10%)
Active Power = ± 1% at 1 watt resolution
Apparent Power = ± 1% at 1 volt-amp resolution
Power Factor = ± 3% at 0.01 resolution
Crest Factor = ± 10% at 0.1 resolution
Energy = ± 1% at 0.1 kilowatt-hour resolution
Output Measurement Accuracy: GUI Current = ± 1% at 0.01 amp resolution (above 0.15 amp)
Voltage = ± 1% at 0.1 volt resolution (nominal ± 10%)
Active Power = ± 1% at 1 watt resolution
Apparent Power = ± 1% at 1 volt-amp resolution
Power Factor = ± 3% at 0.01 resolution
Crest Factor = ± 10% at 0.1 resolution
Energy = ± 1% at 1 watt-hour resolution
Optional Accessories

EMTH-1-1 Combination Temperature/Humidity Probe, 10ft (3m)
EMCU-1-1B Environmental Monitor adding:
   - Two (2) EMTH-1-1 temperature/humidity ports (one probe included)
   - One (1) EMWS-1-1 water sensor port (probe sold separately)
   - Four (4) dry contact (NO/NC) monitoring points
   - One (1) 8-bit analog-to-digital converter (0 to 5VDC)

KIT-STEYE-01 or -10 provides access to key metrics through Bluetooth SPM (Sentry® Power Manager):
   - Monitor and manage multiple PDUs from a single point
   - Monitor and manage alarm conditions
   - Create reports and trends on stored data
   - Analyze power usage per phase
   - Optional appliance or virtual version
   - Vmware Ready2

Mounting Brackets:
   - Buttons (KIT-0020) included for tool-less mounting
   - Custom mounting options available. Contact Bomara Associates

Cable Retention Devices for non-locking cords:
   - Ezip
   - Cable Sleeve


* Order PTCORD separately. Choose L6-20P, CEE 7/7 Schuko, IEC60309 2P+PE, or BS1363

 